18 Ah batteries are required to meet 24‑hour standby requirements.
9.4.2

Minimum Standby UPS Power

The minimum UPS power required (in watts) = Total UPS Current (from the Calculating
Standby Current table) x 120 (voltage) x required hours of standby + 20% (storage).
9.4.3

Estimated BTU Load

The estimated BTU load for the system is calculated as follows: Total UPS Current (from the
Calculating Standby Current table) x AC voltage x 3.4 = Estimated BTU load