6 | NETWORK VARIABLE CHARTS

4.
NETWORK VARIABLE CHARTS
CAUTION
This system adopts the manner of shared network variable to manage
A/C system, which cannot access the appointed A/C within central
A/C system, until the corresponding network variable is modified
to the one that is intended to access. This device consists of two
transceivers (the following called Main controller and Auxiliary
controller for short); Main controller is responsible for querying
and setting of 32 sets air conditioners with addresses of 0~31 and
unified setting all the air conditioners (64 sets at most), and Auxiliary
controller is responsible for querying and setting of 32 sets air
conditioners with addresses of 32~63.
4.1.
NETWORK VARIABLES OF MAIN CONTROLLER
There are 4 network variables of main controller, as follows:
NetWork Variables of setting Main controller
NO.
Meaning
Name
1
Baud rate
nciUARTBaud
2
Waiting time
nciWaitRespTime
3
period
nciWaitTime
Network variables assigned to air conditioners (address 0~31)
Each air conditioner is assigned 3 input network variables(used for
setting) and 4 output network variables (used for query). As the
following figure:
The air conditioner with the address (n-1)
nviSetWorkMode [n]
nviSetFanSpeed [n]
nviSetTemp [n]
6 720 862 467 (2017/05)
Type
Definition
SNVT_count
0: 1200bps
Use for setting the baud rate of Rs
1: 2400bps
485 port(The fixed value is 2)
2:4800bps
Initial value=2
SNVT_count
Initial value=
When waiting the response time,
100ms
give a WaitRespTimer value for the
timer while initialisation and when
the timer is time-out that means no
data recieved. (Suggest the setting
value should not less than 100ms)
SNVT_count
Initial value=
Adjust
300ms
and affect the network variable
updating,then give a WaitTimer
value
initialisation. (Suggest the setting
value should not less than 100ms)
nvoWorkModeFan [n]
nvoSetTemp [n]
nvoIndoorTemp [n]
nvoWorkState [n]
Specifications
the
scanning
period
for
the
timer
while
CLIMATE 5000 VRF