KRE 2 = 0
Turn off dim/bright checks:
KDP = 0
Example 3 - 4 phase controller
Description: Four phase intersection controller with two vehicle and two
Each pedestrian phase is monitored with a single current sensor (see example 2
for separate wait and pedestrian monitoring using two current sensors per phase)
The configuration commands are detailed below.
Enable LMU write access:
AMB = 35
NEC = 249
Allocate function of current sensor 1 to 4:
KPT 1 = 1
KPT 2 = 1
KPT 3 = 12
KPT 4 = 12
Allocate the mains state inputs associated with each current sensor:
Note: Input numbers 1 to 32 on the buffered input connector are referenced as 0
to 31 on the handset commands.
KMS 0 1 = 31
KMS 0 2 = 30
KMS 0 3 = 29
KMS 1 3 = 31
KMS 2 3 = 27
KMS 0 4 = 28
KMS 1 4 = 30
KMS 2 4 = 26
Allocate aspect drive identity to each current sensor:
KAD 1 = 0
KAD 2 = 1
666/HE/43100/000
TC12 Installation, Commissioning & Maintenance Handbook
:sensor 2
pedestrian phases.
:a vehicle phase
:a vehicle phase
:a pedestrian phase, including wait indicators
:a pedestrian phase, including wait indicators
:sensor 1 green is on digital input 32
:sensor 2 green is on digital input 31
:sensor 3 ped green is on digital input 30
:sensor 3 opposing vehicle green is on
:digital input 32 (i.e. phase A green)
:sensor 3 wait is on digital input 28
:sensor 4 ped green is on digital input 29
:sensor 4 opposing vehicle green is on
:digital input 31 (i.e. phase B green)
:sensor 4 wait is on digital input 27
:sensor 1 is phase A
:sensor 2 is phase B
Page 122