6 Electrical installation
6.4.3 Dual circuit feed, special tariff
(Electroplan 3)
A1
L1
Fig. 6.4 Dual circuit feed, special tariff
In this instance the heat pump is operated on two tariffs
(two consumer meters). A permanent supply for the se-
condary consumers (circulation pumps, controller,
etc.) must be ensured via a meter. The low tariff sup-
ply for the compressor and the auxiliary heating is ef-
fected via a second meter and can be interrupted by the
power company at peak times.
Key to Fig. 6.4
:
2 kW
:
4 kW
28
1
+
230 V / 50 Hz
PE N
A2
L2
L3
N
ABB
A12-30-01
T1
T2
T3
Pump
Compressor
Controller
Auxiliary heater
You can set the output of the
auxiliary heating from 4 kW to
2 kW by removing the bypass line,
if required.
230 V / 50 Hz
L
3
L
N
L
N N
L
L
• Remove the jumpers (dashed lines, 3).
• Connect the permanent power supply to the controller
mains feed (2).
• Connect the low tariff power supply to the low tariff
mains feed (1).
• Connect the ripple control signal relay to terminal 13
"EVU", if required by the power company. This signal
blocks the heat pump when the contact is closed (see
Fig. 6.7).
You will find an overview of the complete wiring dia-
gram in the appendix.
2
+
:
L
N
PE
2 kW
:
4 kW
L
N
S S B B A Z N
L L
Installation instructions geoTHERM VWS 0020046310_01