8 Control system
Display shown
Menu A: Installation assistant
Installation
Language selection
Language
>Select
Installation assistant
Hydraulic scheme
Heat pump type
Electric Wiring Diagram
Accept change
>Select
Table 8.4 Parameters that can be set in the Code level (cont.)
62
Description
You will be guided through the Installation Assistant,
Menus A1 and A2, during the initial commissioning of
the heat pump.
The Installation Assistant appears automatically du-
ring initial commissioning.
Language : Set the local language
A1
During the initial installation the controller always
>GB English
starts with this menu (Installation Assistant).
A2
The hydraulic and electroplans must be set by the
installer during initial commissioning.
3
The heat pump type has already been set at the fac-
tory and may not be changed!
5
1
Hydraulic plan:
Yes
1 = no buffer cylinder, no DHW cylinder
2 = with buffer cylinder, no DHW cylinder
3 = no buffer cylinder, with DHW cylinder
4 = with buffer cylinder, with DHW cylinder See Figs.
6.8 to 6.11.
Heat pump type:
Type
29
30
31
Electroplan:
1 = all on the high tariff (see Fig. 6.2).
2 = low tariff for the compressor (see Fig. 6.3).
3 = low tariff for the compressor and electric
auxiliary heating (see Fig. 6.4).
Accept change: Yes/No;
"Yes" means that all the set values will be saved.
Description
VWS 61/2 230 V
VWS 81/2 230 V
VWS 101/2 230 V
Installation instructions geoTHERM VWS 0020046310_01