8.8

Displays in the code layer

The Code layer has different areas in which you can
change parameters or merely view them, depending on
the context. The context can always be recognised from
the menu name.
Menu C: Set parameters for the heating system
Menu D: Perform diagnostics
Menu I: Display general information
Menu A: Installation assistant
Your code entry is reset again 15 minutes after your last
change in the Code level (actuation of one of the dials).
To gain entry to the Code level again after that, you will
have to enter the code once more.
Display shown
Menu C: Set parameters for the heating
system
Code layer
change
Code number:
> 0 0 0 0
Accept change?
>Set figures
<HK2>
Parameters
Type
Heating curve
Max limit outs.temp.
Comp. starts at
>Select temperature
<HK2>
Parameters
Type
Max limit outs.temp.
>Select temperature
Buffer tank
Information
Setpoint flow temp.
T buffer top <VF1>
T Buff.Bot OffsetRF1
Table 8.4 Parameters that can be set in the Code level
Installation instructions geoTHERM VWS 0020046310_01
Description
In Menus C1 to C9 you can set the
parameters for the various functions of the heat
pump.
Menu for changing the code number.
C1
You can replace the standard code 1000 with a user-
defined four-digit code here.
Note: If you change the code, make a note of the
new code, otherwise you will not be able to make
any more changes in the code level!
No
Type: Direct circuit (for direct hydraulics),
C2
Mixer circuit (for buffered hydraulics),
Fixed value (can only be set via vrDIALOG 810/2).
direct circuit
Heating curve: Adjustable heating curve (not with
0.80
fixed value).
>21°C
Maximum limit outside temperature Temperature
-120°min
limit for switching off heating mode (summer func-
tion).
Comp. starts at: Set the degree minutes until com-
pressor start (only with direct hydraulics)
This display appears if "Fixed value" has been set via
C2
vrDIALOG 810/2.
Fixed value
>21°C
If a VR 60 is connected, this menu appears several
times (for each heating circuit).
This display is only shown when a buffer cylinder is
C3
used (e.g. Hydraulic Plans 2 and 4).
41°C
Setpoint flow temp.: Target flow temperature
29°C
T buffer top VF1: Temperature at the buffer cylin-
25°C
der top sensor VF1
T buffer bottom RF1: Temperature at the buffer cy-
linder bottom sensor RF1
(see Section 8.4.3)
Control system 8
Factory setting
1000
0.3
22 °C
57