Chapter 2
Operator display
This chapter shows how to:
Install a Tracer AH540/541 stand-alone operator display
Connect a portable operator display to a Tracer AH540/541 controller
Set up the operator display
Installing the stand-alone operator
display
With the attached cable, the stand-alone operator display (see Figure 5)
can be mounted up to 10 ft (3 m) from the Tracer AH541 controller. You
can extend this distance up to 150 ft (46 m) using four-conductor wire and
the included pig-tail connectors. Alternately, use three twisted-pair wires.
Trane recommends the following four-conductor wires:
Plenum 18 AWG, Trane part number 400-2059
Plenum 22 AWG, Trane part number 400-2020
Non-plenum, Trane part number 400-1005
Figure 5. Tracer AH541 stand-alone operator display
CAUTION
Avoid Equipment Damage!
To clean the operator display, use a cloth dampened with commercial
liquid glass cleaner. Spraying water or cleansers directly on the screen
may result in equipment damage.