Trane Tracer AH540 Setup And Operation page 88

Air-handler controller
Hide thumbs Also See for Tracer AH540:
Table of Contents

Advertisement

Chapter 5 Configuration
Table 42. Space temperature setpoint and limit configuration
Default setpoint
Occupied heating setpoint
Occupied cooling setpoint
Occupied standby heating setpoint
Occupied standby cooling setpoint
Unoccupied heating setpoint
Unoccupied cooling setpoint
Heating setpoint low limit
Cooling setpoint low limit
Heating setpoint high limit
Cooling setpoint high limit
Thumbwheel setpoint
1 The heating and cooling setpoint high and low limits only apply to the occupied and occupied standby setpoints and are never
applied to the unoccupied setpoints.
Table 43. Space temperature control discharge air temperature setpoint and limit configuration
Setpoints and limits
Unoccupied heating discharge air temperature set-
point
Unoccupied cooling discharge air temperature set-
point
Electric heat discharge air temperature high limit
1 Electric heat capacity is reduced if the discharge air temperature exceeds this limit.
78
Table 41. Local zone sensor fan switch configuration
Parameter
Zone sensor fan switch
1
1
1
1
1
Valid range
Enabled or disabled
Valid range
40 to 115°F (4.44 to 46.1°C)
40 to 115°F (4.44 to 46.1°C)
40 to 115°F (4.44 to 46.1°C)
40 to 115°F (4.44 to 46.1°C)
40 to 115°F (4.44 to 46.1°C)
40 to 115°F (4.44 to 46.1°C)
40 to 115°F (4.44 to 46.1°C)
40 to 115°F (4.44 to 46.1°C)
40 to 115°F (4.44 to 46.1°C)
40 to 115°F (4.44 to 46.1°C)
Disable or enable
Valid range
38 to 150°F (3.3 to 65.6°C)
35 to 150°F (1.7 to 65.6°C)
70 to 200°F (21.1 to 93.3°C)
Default
Enabled
Default value
71°F (21.7°C)
74°F (23.3°C)
67°F (19.4°C)
78°F (25.6°C)
60°F (15.6°C)
85°F (29.4°C)
40°F (4.4°C)
40°F (4.4°C)
104°F (40°C)
104°F (40°C)
Enable
Default value
100°F (37.8°C)
55°F (12.8°C)
115°F (46.1°C) draw-through
135°F (57.2°C) blow-through
CNT-SVX05B-EN