Trane Tracer AH540 Setup And Operation page 87

Air-handler controller
Hide thumbs Also See for Tracer AH540:
Table of Contents

Advertisement

Table 38. Outdoor air damper configuration
Parameter
Economizer control
Economizer temperature (dry bulb)
Occupied minimum position
Occupied standby minimum position
Low ambient lockout setpoint
3
Ramp time
1 Occupied standby minimum damper position only applies to space temperature control operation.
2 This is the outdoor air temperature below which the outdoor air damper will always be closed.
3 Adjustable open time for the outdoor air damper to open from 0% to minimum position.
Table 39. DX cooling configuration
Parameter
Ambient lockout setpoint
Discharge low limit setpoint
3
Coil defrost setpoint
Compressor minimum On timer
Compressor minimum Off timer
1 If outdoor air temperature is less than the compressor lockout temperature DX cooling is disabled.
2 If discharge air temperature is less than this setpoint the controller will start reducing DX cooling capacity.
3 When the universal analog input is configured for evaporator refrigerant temperature, and applied to the suction line of a
split DX system; if the evaporator refrigerant temperature is below the defrost setpoint the controller will reduce DX cooling
capacity.
CNT-SVX05B-EN
1
2
Valid range
1
-40 to 122ºF (-40 to 50ºC)
2
32 to 122ºF (0 to 15ºC)
20 to 40ºF (-6.67 to 4.44ºC)
3 to 20 minutes
3 to 20 minutes
Table 40. Dehumidification control configuration
Parameter
Occupied space RH setpoint
Occupied space RH offset
Unoccupied space RH setpoint
Unoccupied space RH offset
Reheat stages allowed
1 Setting the occupied space RH setpoint to 0% disables occupied dehumidification con-
trol; likewise, setting the unoccupied space RH setpoint to 0% disables unoccupied
dehumidification control.
2 The space RH offset value is subtracted from the space RH setpoint to determine the
dehumidification control termination setpoint.
3 Number of electric heat stages allowed for dehumidification control.
Valid range
Enable or disable
32°F to 122°F (0°C to 50°C)
0 to 100%
0 to 100%
-40°F to 32°F (-40°C to 0°C)
0–30 minutes
Valid range
1
0–100%
2
0–100%
1
0–100%
2
0–100%
0–6 stages
3
Configuration
Default value
Enable or disable
50°F (10°C)
15%
10%
-20°F (-28.9°C)
5 minutes
Default value
50ºF (10ºC)
45ºF (7.22ºC)
30ºF (-1.11ºC)
3 minutes
3 minutes
Default value
60%
10%
60%
10%
6
(all stages available)
77