Chapter 1 Overview
Figure 1. Operator display models
2
Additional components
The Tracer MP581 controller requires additional components for certain
applications and has several options for adding an operator display.
Operator display models
The operator display is available in three models (see Figure 1):
Door-mounted operator display
•
Stand-alone operator display, for mounting up to 150 ft (46 m) from
•
the controller
Portable operator display with carrying case
•
Door-mounted
operator display
Stand-alone
operator display
Sensors
The Tracer MP581 supports the following sensors:
Zone temperature sensors (thermistors and linear resistance for
•
thumbwheels)
•
Linear 0–20 mA, such as humidity sensors
Pressure sensors (use only the Trane 5 Vdc pressure-sensor kit—part
•
number 4020 1159)
Linear 0–10 Vdc, such as indoor air-quality sensors
•
Resistance temperature detectors (up to four)
•
Motion sensors, time clocks, and other binary switch devices
•
The Rover service tool is required to configure Tracer MP581 inputs for
all types of sensors.
Note:
The Tracer MP581 supports all Trane zone sensors but does not
support fan switches (HIGH, MED, LOW, AUTO, and OFF).
Portable
operator display
CNT-SVN01C-EN