Trane Tracer AH540 Setup And Operation page 112

Air-handler controller
Hide thumbs Also See for Tracer AH540:
Table of Contents

Advertisement

Appendix
Table 71. Space temperature control operation based on effective heat/cool output (continued)
Application mode input
(nviApplicMode)
Auto
Auto
Auto
Heat
Morning warm-up
Cool
Night purge
Pre-cool
102
Heat/cool mode input
(nviHeatCool)
Emergency heat
Fan only
Not present
Any state
Any state
Any state
Any state
Any state
Effective heat cool mode
output
(nvoHeatCool)
Determined by controller
Fan only
Determined by controller
Heat
Morning warm-up
Cool or dehumidifying
Night purge
Pre-cool
Unit operation
Fan enabled
Heating enabled
Cooling disabled
Damper enabled
Fan enabled
Heating disabled
Cooling disabled
Damper disabled
Fan enabled
Heating enabled
Cooling enabled
Damper enabled
Fan enabled
1
Heating enabled
Cooling disabled
Damper ventilation enabled
Economizer disabled
Fan enabled
Heating enabled
Cooling disabled
Damper closed
Fan enabled
1
Heating disabled
Cooling enabled
Damper enabled
Fan enabled
Heating disabled
Cooling disabled
Damper ventilation disabled
Economizer enabled
Fan enabled
Heating disabled
Cooling enabled
Damper ventilation disabled
Economizer enabled
CNT-SVX05B-EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tracer ah541

Table of Contents