Appendix
106

Input sensor tables

Table 73. Trane zone sensor hard-wired setpoint thumbwheel
Setpoint
50°F (10.0ºC)
58°F (14.4ºC)
66°F (18.9ºC)
70°F (21.1ºC)
74°F (23.3ºC)
78°F (25.6ºC)
82°F (27.8ºC)
86°F (30.0ºC)
90°F (32.2ºC)
Table 74. Hard-wired 10 k
Temperature
Resistance (kΩ)
0ºF (17.8ºC)
87.5
5°F (-15.0ºC)
74.6
10°F (-12.2ºC)
63.8
15°F (9.4ºC)
54.6
20°F (6.7ºC)
46.9
25°F (3.9ºC)
40.4
30°F (-1.1ºC)
34.8
35°F (1.7ºC)
30.2
40°F (4.4ºC)
26.2
45°F (7.2ºC)
22.8
50°F (10.0ºC)
20.0
55°F (12.8ºC)
17.5
60°F (15.6ºC)
15.3
65°F (18.3ºC)
13.5
70°F (21.1ºC)
11.9
75°F (23.9ºC)
10.5
Resistance
889.4 Ω
733.6 Ω
500.0 Ω
422.1 Ω
344.2 Ω
266.4 Ω
188.5 Ω
thermistor values
Temperature
(continued)
77°F (25.0ºC)
80°F (26.7ºC)
85°F (29.4ºC)
90°F (32.2ºC)
95°F (35.0ºC)
100°F (37.8ºC)
105°F (40.6ºC)
110°F (43.3ºC)
115°F (46.1ºC)
120°F (48.9ºC)
125°F (51.7ºC)
130°F (54.4ºC)
135°F (57.2ºC)
140°F (60.0ºC)
145°F (62.8ºC)
150°F (65.6ºC)
577.9 Ω
110.6 Ω
Resistance (kΩ)
(continued)
10.0
9.3
8.2
7.3
6.5
5.8
5.2
4.7
4.2
3.8
3.4
3.1
2.8
2.5
2.3
2.1