Analog Inputs - Trane Tracer AH540 Setup And Operation

Air-handler controller
Hide thumbs Also See for Tracer AH540:
Table of Contents

Advertisement

Table 5. Analog input functions and locations
AH540
Input
Terminal label
label
IN 1
TB31/1
IN
TB31/2
GND
IN 2
TB32/1
IN
TB32/2
GND
IN 3
TB33/1
IN
TB33/2
GND
IN 4
TB34/1
IN
TB34/2
GND
IN 5
TB35/1
IN
TB35/2
GND
IN 6
TB36/1
IN
TB36/2
GND
TB43
4
IN 13
Duct
static
1 See Appendix for analog input sensor curves (Table 73, Table 74, Table 75, Table 76, and Table 77).
2 Sensor type: Switched resistance fan auto = 2320
3 Sensor type RTD averaging sensor, 1000
4 This input is located on the main control board.
CNT-SVX05B-EN

Analog inputs

The Tracer AH540/541 controller has eight analog inputs. Table 5
describes the function of each of the analog inputs. Each function is
described in the following paragraphs. For an explanation of the diagnos-
tics generated by each input, see Chapter 6, "Verifying operation and
communication." For more information about how the controller operates,
see Chapter 4, "Sequence of operation."
AH541
Factory
Field
terminal
terminal
label
label
J31
IN1
Space temperature
J32
IN2
Local setpoint
J33
IN3
Fan mode switch
J34
IN4
Discharge air
temperature
J35
IN5
Outdoor air
temperature
J36
IN6
Mixed-air
temperature
Space relative
humidity
CO
Entering water
temperature
Evaporator refriger-
ant temperature
Generic temperature
J43
Duct
Duct static pressure
static
, ±5%, fan off = 4870
at 0°C, platinum 385 curve.
Function
Sensor type
10 kΩ thermistor
1 kΩ
potentiometer
2
Switched
resistance
10 kΩ thermistor
10 kΩ thermistor
3
RTD
Current:
4–20 mA
sensor
Current:
2
4–20 mA
10 kΩ thermistor
10 kΩ thermistor
10 kΩ thermistor
Duct static-
pressure sensor
(Trane part num-
ber 4020 1159)
, ±5%.
Analog inputs
1
Valid ranges
5°F to 122°F
(-15°C to 50°C)
50°F to 85°F
(10°C to 29.4°C)
Off (4870 Ω ±5%)
Auto (2320 Ω ±5%)
–40°F to 212°F
(-40°C to 100°C)
-40°F to 212°F
(-40°C to 100°C)
-40°F to 212°F
(-40°C to 100°C)
0 to 100%
0 to 2000 ppm
-40°F to 212°F
(-40°C to 100°C)
-40°F to 212°F
(-40°C to 100°C)
-40°F to 212°F
(-40°C to 100°C)
0 to 1250 Pa
0 to 5.02 in. water
17

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tracer ah541