CNT-SVX05B-EN
Table 75. Hard-wired 1 k
Temperature
Resistance (kΩ)
0°F (-17.8ºC)
930.3
5°F (-15.0ºC)
941.2
10°F (-12.2ºC)
952.1
15°F (-9.4ºC)
963.0
20°F (-6.7ºC)
973.9
25°F (-3.9ºC)
984.8
30°F (-1.1ºC)
995.7
32°F (0.0ºC)
1000.0
35°F (1.7ºC)
1006.5
40°F (4.4ºC)
1017.4
45°F (7.2ºC)
1028.2
50°F (10.0ºC)
1039.0
55°F (12.8ºC)
1049.8
60°F (15.6ºC)
1060.7
65°F (18.3ºC)
1071.5
70°F (21.1ºC)
1082.2
75°F (23.9ºC)
1093.0
Table 76. Hard-wired relative humidity sensor values
Relative
Current (mA)
humidity (%)
4
5
6.3
6
12.5
7
18.8
8
25
9
31.3
10
37.5
11
43.8
12
50
13
56.3
14
62.5
15
68.8
16
75
17
81.3
18
87.5
19
93.8
20
100
mixed-air sensor RTD values
Temperature
(continued)
77°F (25.0ºC)
80°F (26.7ºC)
85°F (29.4ºC)
90°F (32.2ºC)
95°F (35.0ºC)
100°F (37.8ºC)
105°F (40.6ºC)
110°F (43.3ºC)
115°F (46.1ºC)
120°F (48.9ºC)
125°F (51.7ºC)
130°F (54.4ºC)
135°F (57.2ºC)
140°F (60.0ºC)
145°F (62.8ºC)
150°F (65.6ºC)
Relative
humidity (%)
0
Input sensor tables
Resistance (kΩ)
(continued)
1097.3
1103.8
1114.6
1125.3
1136.1
1146.8
1157.5
1168.3
1179.0
1189.7
1200.4
1211.0
1221.7
1232.4
1243.0
1253.7
Current (mA)
0
4
10
5.6
20
7.2
30
8.8
40
10.4
50
12
60
13.6
70
15.2
80
16.8
90
18.4
100
20