Table 71. Space temperature control operation based on effective heat/cool output (continued)
Application mode input
(nviApplicMode)
Off
Test
Emergency heat
Fan only
1 Heating capacity can be used to control the discharge air temperature to the discharge air temperature setpoint.
Table 72. Discharge air temperature control operation based on effective heat/cool output
Application
mode input
(nviApplicMode)
Auto
Heat
Morning warm-up
Cool
Night purge
CNT-SVX05B-EN
Heat/cool mode input
(nviHeatCool)
Any state
Any state
Any state
Any state
Effective heat
cool mode output
(nvoHeatCool)
Determined by controller
Heat
Morning warm-up
Cool
Night purge
Unit operation based on heat/cool mode
Effective heat cool mode
output
(nvoHeatCool)
Off
Determined by controller
Determined by controller
Fan only
Application mode
output
(nvoApplicMode)
Determined by controller
Heat
Heat
Cool
Cool
Unit operation
Fan disabled
Heating disabled
Cooling disabled
Damper disabled
Fan enabled
Heating enabled
Cooling enabled
Damper enabled
Fan enabled
Heating enabled
Cooling enabled
Damper enabled
Fan enabled
Heating disabled
Cooling disabled
Damper disabled
Unit operation
Fan enabled
Heating enabled
Cooling enabled
Damper enabled
Fan enabled
Heating enabled
Cooling disabled
Damper ventilation enabled
Economizer disabled
Fan enabled
Heating enabled
Cooling disabled
Damper disabled
Fan enabled
1
Heating disabled
Cooling enabled
Damper enabled
Fan enabled
Heating disabled
Cooling disabled
Damper ventilation disabled
Economizer enabled
103