Output - Honeywell Excel 10 W7752D User Manual

Fan coil unit controllers lns plug-ins
Table of Contents

Advertisement

EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE

Output

The available options for output configurations with the default values shown are listed in Table 16. See section "Configurations"
on page 12 for more information about parameters.
Table 16. FCU Controller output configuration options and default configurations
function
configuration options
model
2-pipe (1 valve)
system type
4-pipe (2 valves)
no fan
1-speed fan
fan type
2-speed fan
3-speed fan
reheat
relay 4
network control (free use)
(reheat relay)
not used
not used
output 1
cooling
3
(triac 1 and 2)
heating
1
control
heat/cool changeover
floating
floating-mid
output 1
1-stage
3
(triac 1 and 2)
2-stage
type
3-stage
PWM
thermal
not used
output 2
cooling
3
(triac 3 and 4)
heating
1
control
heat/cool changeover
floating
floating-mid
output 2
1-stage
3
(triac 3 and 4)
2-stage
type
3-stage
PWM
thermal
Notes:
1. The output mode settings apply only to a 4-pipe system. In a 2-pipe system, output 1 will always operate in the changeover
mode.
2. The floating-mid option is for changeover applications, only, and uses only one of the two outputs.
3. The operation of the triacs based upon the output type is given in Table 12 on page 21 and in Table 14 on page 23.
4. W7754K1001 is equipped with a low-voltage digital output suitable for connection to a solid-state relay employed for low-
voltage PWM control in high-current electric reheat applications; this digital output is activated if output 1 type is set to either
"PWM" or "thermal".
EN2B-0285GE51 R0909
default configuration
D,F
4-pipe
3-speed
reheat
heating
2
floating
cooling
2
floating
W7752
4
E,G,J
K
4-pipe
4-pipe
3-speed
not used
heating
floating
PWM
cooling
floating
thermal
26
default configuration
W7754
L
M
N
2-pipe
4-pipe
3-speed
not used
heating
ther-
ther-
floating
mal
mal
cooling
ther-
floating
mal
P
reheat
floating
floating

Hide quick links: