NV name
field name
nvoUnitStatus
heat_output_primary
nvoUnitStatus
heat_output_
secondary
nvoUnitStatus
cool_output
nvoUnitStatus
fan_output
nvoUnitStatus
in_alarm
nvoWindow
value
nvoWindow
state
nroPgmVer
id[0]
nroPgmVer
id[1]
nroPgmVer
id[2]
nroPgmVer
id[3]
nroPgmVer
major_ver
nroPgmVer
minor_ver
Table C4. Output Variables for Excel 10 FCU Controllers.
digital
engineering units:
state
English (metric) or states plus
or
range
value
SNVT_lev_percent
0 to 100%
163.835% = INVALID
SNVT_lev_percent
0 to 100%
163.835% = INVALID
SNVT_lev_percent
0 to 100%
163.835% = INVALID
SNVT_lev_percent
0 to 100%
UBYTE
NO_ALARM
0
ALARM
1
ALARM_NOTIFY_DISABLED
255
SNVT_switch.value
0 to 100%
SNVT_switch.state
CLOSED
0
OPEN
1
NO_WINDOW
255
UBYTE, 70 = F
UBYTE, 67 = C
UBYTE, 85 = U
UBYTE, 50 = 2
UBYTE, 0 to 255
UBYTE, 0 to 255
EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE
default
This output variable reports the actual heating output value. Any
change forces nvoUnitStatus to be transmitted immediately.
This output variable reports the reheat output value.
This output variable reports the actual cooling output value. A
change of more than 1% forces nvoUnitStatus to be transmitted
immediately.
This output variable reports the actual fan speed level.
This output variable reports the actual alarm status of the controller
and is set to ALARM_NOTIFY_DISABLE when nviManualMode =
SUPPRESS_ALARMS.
0
This output variable reports the status of the window sensor. It
(at application restart)
allows the locally-wired window sensor to be used by other nodes
on the network.
NO_WINDOW
See above.
(at application restart)
This output variable identifies the Excel 10 node type by an eight
byte constant describing the node type, major and minor functional
release number and bug fix. First character.
Second character.
Third character.
Fourth character.
Major Functional Release Number:
1.
Add or delete a network variable (NV), nv field.
2.
Change the name of a nv or nv field.
3.
Range or type (short / long) of data in a nv field is changed.
4.
Enumerated value list of a nv field is changed.
NOTE: Algorithm changes or bug fixes may also be included.
Minor Functional Release Number:
63
comments
EN2B-0285GE51 R0909