EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE
NV name
field name
nciFcuConfig
output_type[0]
nciFcuConfig
output_type[1]
nciFcuConfig
valve_reverse_0
nciFcuConfig
valve_reverse_1
nciFcuConfig
fan_interlock_0
nciFcuConfig
fan_interlock_1
EN2B-0285GE51 R0909
Table C2. Configuration Variables for Excel 10 FCU Controllers
digital
engineering units:
state
English (metric) or states
or
plus range
value
BYTE
FLOATING
0
ONE_STAGE
1
TWO_STAGE
2
THREE_STAGE
3
PWM
4
THERMAL
5
FLOATING_MID
6
BYTE
FLOATING
0
ONE_STAGE
1
TWO_STAGE
2
THREE_STAGE
3
PWM
4
THERMAL
5
FLOATING_MID
6
Bit
DIRECT
0
REVERSE
1
Bit
DIRECT
0
REVERSE
1
Bit
NO
0
YES
1
Bit
NO
0
YES
1
default
FLOATING
This configuration variable specifies the output type to drive the
connected actuator for the output 1:
FLOATING/FLOATING_MID - This setting considers valve_reverse[]
and cycle_time[]. Synchronization is performed at every restart and at
least once per day.
ONE_STAGE - Triac 2 is not used.
TWO_STAGE/THREE_STAGE - Triac 1 and 2 used (triac 1 and 2 both
ON for stage 3). When configured as multistage, cycle_time and
min_stage_off_time are considered.
PWM/THERMAL - Triac 2 is not used. Triac 1 operates as a pulse-
width modulated output, and the cycle time must be specified in
cycle_time[]. For PWM outputs, PwmZeroPosn and PwmFullPosn must
also be specified.
FLOATING
This configuration variable specifies the output type to drive the
connected actuator for the output 2 (see above).
DIRECT
This configuration variable applies to only those outputs that have been
configured as FLOATING, PWM, or THERMAL and specifies the
direct/reverse operation of output 1.
DIRECT
This configuration variable applies only to those outputs that have been
configured as FLOATING, PWM, or THERMAL and specifies the
direct/reverse operation of output 2.
NO
This configuration variable configures an interlock between fan and
output 1 to provide equipment protection for electric heat or
compressor. fan_interlock_0=1 enables interlock, which guarantees
output1 to be driven only when the fan is running.
NO
This configuration variable configures an interlock between fan and
output 2 to provide equipment protection for electric heat or
compressor. fan_interlock_1=1 enables interlock, which guarantees
output2 to be driven only when the fan is running.
42
comments