Honeywell Excel 10 W7752D User Manual page 45

Fan coil unit controllers lns plug-ins
Table of Contents

Advertisement

NV name
field name
nciFcuConfig
cycle_time[0]
nciFcuConfig
cycle_time[1]
nciFcuConfig
min_stage_off_time[0]
nciFcuConfig
min_stage_off_time[1]
nciFcuConfig
reheat_config
nciFcuConfig
PwmZeroPosn
nciFcuConfig
PwmFullPosn
nciFcuGains
si_pid_Xp[0]
Table C2. Configuration Variables for Excel 10 FCU Controllers
digital
engineering units:
state
English (metric) or states
or
plus range
value
SNVT_time_sec
0 to 1200s for stage output
0 to 600s for floating output
20 to 600s for PWM output
SNVT_time_sec
0 to 1200s for stage output
0 to 600s for floating output
20 to 600s for PWM output
SNVT_time_sec
0 to 600 seconds
SNVT_time_sec
0 to 600 seconds
BYTE
REHEAT
0
FREE_USE
1
REL_NOT_USED
255
SNVT_lev_percent
0 to 100%
SNVT_lev_percent
0 to 100%
SNVT_temp_p
2.25 to 180 DDF
(1.25 to 100 K), 0 = Disable
EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE
default
150 s for floating
This configuration variable specifies for the output 1 configured as
• FLOATING: the runtime of the valve (time to run from fully closed to
fully open)
• PWM: the cycle time
• ONE_STAGE, TWO_STAGE, and THREE_STAGE: minimum ON
time before switching to the next stage.
150 s for floating
This configuration variable specifies for the output 2 configured as
• FLOATING: the runtime of the valve (time to run from fully closed to
fully open)
• PWM: the cycle time
• ONE_STAGE, TWO_STAGE, and THREE_STAGE: minimum ON
time before switching to the next stage.
90 s
This configuration variable is used only for ONE_STAGE,
TWO_STAGE, and THREE_STAGE output 1 and specifies the mini-
mum OFF time before switching to the next stage.
90 s
This configuration variable is used only for ONE_STAGE,
TWO_STAGE, and THREE_STAGE output 2 and specifies the mini-
mum OFF time before switching to the next stage
REHEAT
This configuration variable specifies the usage of the reheat relay.
FREE_USE specifies that the relay is controlled via the network using
the nviReheatRelay .
0%
This configuration variable specifies the zero position for PWM
actuators. This setting applies to PWM actuators only and is used for
both actuators if both are configured as PWM actuators.
100%
This configuration variable specifies the fully open position for PWM
actuators. This setting applies to PWM actuators only and is used for
both actuators if both are configured as PWM actuators.
36 DDF (20 K)
This configuration variable specifies the throttling range for use in the
proportional portion of the PID loop gain for the cooling mode. The
minimum configurable value (not including 0 for disabling) is 3.6 DDF
(2 K) for PI or 2.25 DDF (1.25 K) for P control. For versions prior to
1.0.3, the minimum value is 7.2 DDF (4 K).
43
comments
EN2B-0285GE51 R0909