Honeywell Excel 10 W7752D User Manual page 63

Fan coil unit controllers lns plug-ins
Table of Contents

Advertisement

NV name
field name
nvoSensor
fan_speed_switch
nvoSensor
remote_set_point
nvoSensor
space_temp
nvoSensor
ub_hard_config
nvoSensorOcc
nvoSpaceTemp
Table C4. Output Variables for Excel 10 FCU Controllers.
digital
engineering units:
state
English (metric) or states plus
or
range
value
0 to 65535
SNVT_lev_disc
ST_OFF
0
ST_LOW
1
ST_MED
2
ST_HIGH
3
ST_NUL (No Switch)
255
SNVT_temp_p
-9 to 9 DDF (-5 to 5 K) for
relative
53.6 to 86°F (12 to 30°C) for
absolute
SNVT_temp_p
0 to 104°F (0 to 40°C)
621.806°F (327.67°C) =
INVALID
BYTE
INITIAL
0
W7752D, F
4
W7752E, G
5
INVALID
255
SNVT_occupancy
OC_OCCUPIED
0
OC_UNOCCUPIED
1
OC_NUL (No Sensor)
255
SNVT_temp_p
0 to 104°F (0 to 40°C)
621.806°F (327.67°C) =
INVALID
EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE
default
This output variable indicates the position of the fan speed switch
ON the wall module.
This output variable is the setpoint from the wall module setpoint
knob and may be absolute or relative depending upon
nciWallMod.set_pnt_knob.
This output variable is the measured space temperature.
INITIAL
This output variable is used to establish hardware-dependent
(at application restart)
factory default configuration settings for the Fan Coil Unit
controller. Note that D and F versions and E, G and J versions
differ only in their supply voltage.
OC_NUL
This output variable shows the state of the locally-wired occupancy
(at application restart)
sensor, if one is configured by nciFcuConfig.DI1_config. OC_NUL
means no input is available because it is not bound or not
configured by nciFcuConfig.DI1_config.
INVALID
This output variable is the sensed space temperature at the node
(at application restart)
taken from the locally-wired sensor. It is typically bound to
nviSpaceTemp of another node which may not have its own space
temperature sensor but controls the same space. It is also used for
monitoring purposes, showing the current space temperature used
for the control algorithm. nvoSpaceTemp is transmitted
immediately when its value has changed significantly (> 0.5
delta°C). The reported space temperature includes the offset
correction nciWallMod.si_space_temp_zero_cal. If a space
temperature sensor is not connected or is shorted or if
61