Honeywell Excel 10 W7752D User Manual page 62

Fan coil unit controllers lns plug-ins
Table of Contents

Advertisement

EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE
NV name
field name
nvoFcuStatusP
external_active
nvoFcuStatusP
fan_stages_active
nvoFcuStatusP
output_position[0]
nvoFcuStatusP
output_position[1]
nvoFcuStatusP
reheat_active
nvoFcuStatusP
active_set_pt
nvoFcuStatusP
space_temp
nvoFcuStatusP
rest_bypass_time
nvoHeatOutput
nvoReheat
value
nvoReheat
state
nvoSensor
override_button
nvoSensor
contact_state_DI1
nvoSensor
raw_data[0]
nvoSensor
raw_data[1]
nvoSensor
raw_data[2]
EN2B-0285GE51 R0909
Table C4. Output Variables for Excel 10 FCU Controllers.
digital
engineering units:
state
English (metric) or states plus
or
range
value
Same as nvoFcuStatus
Same as nvoFcuStatus
Same as nvoFcuStatus.
Same as nvoFcuStatus.
Same as nvoFcuStatus
Same as nvoFcuStatus.
Same as nvoFcuStatus.
Same as nvoFcuStatus.
SNVT_lev_percent
0 to 100%
163.835% = INVALID
SNVT_switch.value
0 to 100%
SNVT_switch.state
OFF
0
ON
1
NO_REHEAT
2
Bit
NOT_PRESSED
0
PRESSED
1
Bit
CONTACT_OPEN
0
CONTACT_CLOSED
1
UWORD
0 to 65535
UWORD
0 to 65535
UWORD
default
Same as nvoFcuStatus.
Same as nvoFcuStatus.
Same as nvoFcuStatus.
Same as nvoFcuStatus.
Same as nvoFcuStatus.
Same as nvoFcuStatus.
Same as nvoFcuStatus.
Same as nvoFcuStatus.
This output variable is the heating output which is typically used for
monitoring or bound to a heat actuator node or another Excel 10
controller operating as slave. nvoHeatOutput will be transmitted
immediately when its value has changed significantly (>= 1%), and
periodically according to nciSndHrtBt. The output value represents
the output of the control algorithm but is limited to a range of 0% to
100%.
This output variable reports the actual state of the reheat output. It
can be bound to another Excel 10 controller acting as a slave, or it
can be bound to a third-party reheat node.
See above.
This output variable indicates the status of the override push-
button.
This output variable indicates the state of the digital input.
This output variable contains the analog to digital converter count
measured from the analog value of the temp. sensor, which
represents the measured time during the second part of each A/D
conversion.
Same as above for the fan speed switch.
Same as above for the setpoint knob.
60
comments