Honeywell Excel 10 W7752D User Manual page 57

Fan coil unit controllers lns plug-ins
Table of Contents

Advertisement

NV name
field name
nvoAlarmStatus
error_bit[2]
nvoApplicMode
nvoCoolOutput
nvoDigitInState
value
nvoDigitInState
state
nvoEffectOcc
nvoFanSpeed
value
nvoFanSpeed
state
Table C4. Output Variables for Excel 10 FCU Controllers.
digital
engineering units:
state
English (metric) or states plus
or
range
value
UBYTE
Bit coded Alarm:
ALM_COMFAIL_MANHEAT
1
ALM_COMFAIL_MANCOOL
2
ALM_HW_SW_MISMATCH
4
SNVT_hvac_mode
HVAC_AUTO
0
HVAC_HEAT
1
HVAC_COOL
3
HVAC_OFF
6
SNVT_lev_percent
0 to 100%
163.835% = INVALID
SNVT_switch.value
0 to 100%
SNVT_switch.state
OFF
0
ON
1
NOT_ASSIGNED
255
SNVT_occupancy
OC_OCCUPIED
0
OC_UNOCCUPIED
1
OC_BYPASS
2
OC_STANDBY
3
SNVT_switch.value
0 to 100%
SNVT_switch.state
OFF
0
ON
1
EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE
default
See above.
HVAC_OFF
This output variable is used to coordinate the slave devices with
(at application restart)
the master controller. It reflects the current heat/cool medium
based upon the available supply energy. This is required for con-
figurations with heat/cool changeover. HVAC_OFF switches the
heat/cool control OFF while still providing frost protection and
reporting status and alarms.
This output variable is the cooling output which is typically used for
monitoring or bound to a cooling actuator node or another con-
troller operating as slave. nvoCoolOutput will be transmitted
immediately when its value has changed significantly (>= 1%), and
periodically according to nciSndHrtBt. The output value represents
the output of the control algorithm but is limited to a range of 0% to
100%.
This output variable indicates the binary state of the controller's
digital input which can be configured to support a window contact,
an occupancy/movement sensor, an air flow contact, or a heat/cool
changeover contact. It can be bound to another Excel 10 controller
or a third party node.
See above.
This output variable reflects the effective occupancy mode derived
from the time schedule, occupancy sensor, override button, and
network occupancy override.
0 (at application restart)
This output variable reports the fan speed for the controller. It can
be bound to another Excel 10 controller with a fan connected or to
a third-party fan node.
NO_FAN
See above.
(at application restart)
55
comments
EN2B-0285GE51 R0909