Controller Performance Specifications - Honeywell Excel 10 W7752D User Manual

Fan coil unit controllers lns plug-ins
Table of Contents

Advertisement

Controller Performance Specifications

Power:
W7752D and W7752E; W7754K,M,N,P
230 Vac +10%, -15%, 50/60 Hz.
W7752F and W7752G
115 Vac +10%, -15%, 50/60 Hz.
W7752J
100 Vac ±6%, 50/60 Hz.
W7754L
24 Vac ±20%, 50/60 Hz.
Operating Temperature:
32...122°F (0...50°C).
Shipping/Storage Temperature:
-40...+158°F (-40...+70°C).
Relative Humidity:
5% to 95% non-condensing
Inputs:
Temperature Sensor:
20k ohm NTC
Setpoint Potentiometer:
10k ohm
Digital Input:
Closed ≤ 400 ohms
Open ≥ 10 K ohms
Outputs:
Triac voltage range:
24 Vac ± 20%.
Triac max. current ratings:
250 mA continuous
650 mA surge for 30 sec.
IMPORTANT:
When any device is energized by a triac, the device
must be able to sink a minimum of 15 mA. If non-
Honeywell motors, actuators, or transducers are to
be used with Excel 10 FCU Controllers, compatibility
must be verified.
Fan relays voltage range:
20 to 253 Vac
Fan relays max. current rating:
3 A
Electric reheat relay voltage range:
20 to 253 Vac
Electric reheat relay max. current rating:
10 A
6 A (UL916)
Interoperability
The Excel 10 FCU Controllers use the LonTalk protocol. They
support the L
M
Functional Profile # 8020 "Fan Coil Unit
ON
ARK
Controller", version 2.0. Fig. 8 shows the implementation
used.
EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE
nviSpaceTemp
nv1
SNVT_temp_p
nviSetPoint
nv2
SNVT_temp_p
nviFanSpeedCmd
nv6
SNVT_switch
nviOccCmd
nv7
SNVT_occupancy
nviApplicMode
nv8
SNVT_hvac_mode
nviSetPtOffset
nv9
SNVT_temp_p
nviWaterTemp
nv10
SNVT_temp_p
nviDischAirTemp
nv17
SNVT_temp_p
nviEnergyHoldOff
nv18
SNVT_switch
nc49 - nciSndHrtBt
nc52 - nciMinOutTm
nc48 - nciRcvHrtBt
nc17 - nciLocation
nc60 - nciSetPnts
nc59 - nciNumValve
nviSensorOcc
SNVT_Occupancy
nviEmerg
SNVT_hvac_emerg
nviReheatRelay
SNVT_switch
NOT SUPPORTED.
Fig. 8. L
11
Hardware
Output
Fan Coil Unit Controller
Object #8020
nvoHeatOutput
nv3
SNVT_lev_percent
Mandatory
Network
nvoCoolOutput
nv4
Variables
SNVT_lev_percent
nvoFanSpeed
nv5
SNVT_switch
nvoTerminalLoad
nv11
SNVT_lev_percent
nvoLoadAbs
nv12
SNVT_power
Optional
nvoDischAirTemp
Network
nv13
SNVT_temp_p
Variables
nvoReheat
nv14
SNVT_switch
nvoSpaceTemp
nv15
SNVT_temp_p
nvoEffectSetPt
nv16
SNVT_temp_p
nvoEffectOcc
nv19
SNVT_occupancy
nvoEnergyHoldOff
nv20
SNVT_switch
nvoUnitStatus
nv21
SNVT_hvac_status
Configuration Properties
SNVT_time_sec
mandatory
SNVT_time_sec
optional
SNVT_time_sec
optional
SNVT_str_asc
optional
SNVT_temp_setpt
mandatory
SNVT_count
optional
Manufacturer
nvoSensorOcc
Defined
SNVT_occupancy
Section
nvoDigitInState
SNVT_switch
Hardware
Input
M
FCU object profile
ON
ARK
EN2B-0285GE51 R0909

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents