FS-8704-06 BACnet IP Driver Manual
6.2

Server Side Connection Parameters

Section Title
Connections
Column Title
Function
Adapter
Adapter Name
Protocol
Specify protocol used
Specify if this Connection should act as a BBMD Server on the
Connection_Type*
network. Refer to Appendix A.5 for more information.
Specify the UDP port that will be used to communicate with
IP_Port*
other BACnet Client devices.
Example
// Server Side Connections
Connections
Adapter
, Protocol
N1
, Bacnet_IP
6.3

Server Side Node Parameters

Section Title
Nodes
Column Title
Function
Node_Name
Provide name for Node
Node_ID
BACnet station address of physical Server node
Protocol
Specify protocol used
Enable or disable COV for this Node. Refer to Appendix A.8 for
Node_Option*
further information.
Specific to Trane applications. The Node type can be defined.
Node_Type*
Refer to Appendix C.2
Certain BACnet Services can be disabled on a BACnet Server Node
Disabled_Services*
when specific requirements necessitate this. Refer to Appendix
A.12 for more information.
Model_Name*
Sets the Model Name Property of the Device Object
5 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available
on specific hardware.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
, Connection_Type
, BBMD
Page 14 of 57
Legal Values
5
N1, N2
BACnet_IP
BBMD, -
Any legal IP port value (1
- 65535); 47808
Legal Values
Up
to
31
alphanumeric
characters
0 - 4194303
BACnet_IP
COV_Enable,
COV_Disable, -
BCU,
Summit
Workstation, -
-, WPM, COV
Up
to
32
alphanumeric
characters

Advertisement

Table of Contents
loading