Driver Manual (Supplement to the FieldServer Instruction Manual) FS-8700-16 Bacnet PTP - Serial APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after June 2009 A Sierra Monitor Company Driver Version: 1.17 Document Revision:...
Page 4 of 32 BACNET PTP DESCRIPTION The BACnet PTP driver allows the FieldServer to transfer data to and from devices using the BACnet protocol over a serial RS-232 physical layer. The FieldServer can emulate either a Server or Client.
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: (888) 509-1970 email: support@fieldserver.com ports. These ports just need to be configured 8917-03...
BACnet PTP Server. The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for BACnet communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays”...
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: (888) 509-1970 email: support@fieldserver.com Legal Values 1-255...
Scan_Interval* Rate at which data is polled FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: (888) 509-1970 email: support@fieldserver.com Legal Values Up to 32 alphanumeric characters One of the Data Array names from “Data_Array”...
BACnet PTP Client. The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for BACnet communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays”...
When using the Trane Tracer Summit Workstation System, this name will appear as the object name FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: (888) 509-1970 email: support@fieldserver.com , Data_Array_Length...
4 Note that Port is not declared in the Server Side Nodes FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: (888) 509-1970 email: support@fieldserver.com Legal Values Up to 32 alphanumeric characters One of the Data Array names from “Data Arrays”...
See the BACnet DFS to determine if a particular object supports this property FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: (888) 509-1970 email: support@fieldserver.com Legal Values One of the Node Names specified in “Server Side Node Descriptors”...
IP/MAC address. The default Network number of a FieldServer is 5. If there is more than one FieldServer on a BACnet intranet with multiple nodes, the default network number of the additional FieldServers will need to be changed and a unique number allocated to each.
Appendix A.4. FieldServer implementation of BACnet priority Arrays When BACnet Output objects are written to the Server side of the FieldServer, an associated write priority is given to each write value. When the FieldServer receives the write value, it stores it to the Map Descriptor Priority Array Table at the specified priority. The Priority Array Table is then scanned and the value with the highest priority is stored to the Data Array location specified by the Map Descriptor.
AcknowledgeAlarm service) and for all subscribed client workstations to be notified of alarm acknowledgements (using EventNotifications of type ACK_NOTIFICATION).. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: (888) 509-1970 email: support@fieldserver.com , Table_Index_Value , Table_User_Value...
COV functionality (SubscribeCOV service) only applies to the Present_Value and Status_Flags properties of BACnet Objects - the SubscribeCOVProperty service is not supported by the FieldServer. For analog Server Map Descriptors the user may optionally configure a COV_Increment value to adjust the reporting threshold.
If the Node Name configured on the BACnet Server Side of the configuration is not being indicated as the Device Name on the BACnet SCADA system, then the FieldServer is not communicating with the SCADA system. If the Device Object's name is being indicated, but the Present_Value shows question marks, then it is likely that the Client side of the FieldServer is not communicating.
McQuay Units are shipped with a default Device instance of the last 6 digits of the McQuay Serial number. Appendix C.2. Trane When new points are added to the FieldServer it is important to restart the Summit Workstation or BCU, otherwise these new points may not be seen by the FieldServer.
NORMAL. Other values: FAULT, OFF-NORMAL, HIGH-LIMIT, LOW-LIMIT, LIFE- SAFETY-ALARM Units This property contains the units associated with the Present_Value property. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 27 of 32...
Page 28
This property is the default value to be used for the Present_Value property when all Relinquish_Default command priority values in the Priority_Array property have a NULL value. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 28 of 32...
Exception Errors is not supported FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: (888) 509-1970 email: support@fieldserver.com Page 32 of 32 Resolution It is normal to receive a few link control messages.