Configuring The Fieldserver As A Simplex Time Recorder Company - 4100 Computer Port Protocol Client; Client Side Connection Parameters - FieldServer FS-8700-41 Driver Manual

Simplex time recorder company - 4100 computer port protocol
Table of Contents

Advertisement

FS-8700-41 Simplex 4100 Driver Manual
5
CONFIGURING THE FIELDSERVER AS A SIMPLEX TIME RE CORDER COMPANY - 4100
COMPUTER PORT PROTOCOL CLIENT
For a detailed discussion on FieldServer configuration, please refer to the relevant instruction manual. The
information that follows describes how to expand upon the factory defaults provided in the configuration files
included with the FieldServer (See ".csv" files provided with the FieldServer).
This section documents and describes the parameters necessary for configuring the FieldServer to communicate
with a Simplex Time Recorder Company - 4100 Computer Port Protocol Server.
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable
the FieldServer for Simplex Time Recorder Company - 4100 Computer Port Protocol communications, the driver
independent FieldServer buffers need to be declared in the "Data Arrays" section, the destination device addresses
need to be declared in the "Client Side Nodes" section, and the data required from the servers needs to be
mapped in the "Client Side Map Descriptors" section. Details on how to do this can be found below.
Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.
5.1
Client S ide Connection Parameters
Section Title
Connections
Column
Function
Title
Specify which port the device is connected to
Port
the FieldServer
Baud*
Specify baud rate
Parity*
Specify parity
Data_Bits*
Specify data bits
Stop_Bits*
Specify stop bits
Protocol
Specify protocol used
Poll Delay*
Time between internal polls
Example
//
Client Side Connections
Connections
Port
, Protocol
, Baud
P8
, Sim4100
, 9600
3
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available
on specific hardware.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
, Parity
, Poll_Delay
, Even
, 0.100s
Legal Values
3
P1-P8, R1-R2
110 – 115200, standard baud rates only.
(Vendor limitation)
Even, Odd, None, Mark, Space
7, 8
1
sim4100
0-32000 seconds, 1 second