FS-8700-40 SBT FSI Driver Manual
6.1

Server Side Connection Descriptors

Section Title
Connections
Column Title
Function
Port
Specify which port the device is connected to the FieldServer
Protocol
Specify protocol used
Enables legacy or enhanced protocol.. MXL panels do not currently
support Enhanced_Protocol, so this parameter must be set to "No"
Enhanced_Protocol
for MXL. The parameter is normally set to "Yes" for XLS, but may be
set to "No" if problems are being experienced.
System_Type
Specifies Siemens Panel type
Echo
Specifies if the server should echo the client's polls
Baud*
Specify baud rate
Parity*
Specify parity
Data_Bits*
Specify data bits
Stop_Bits*
Specify stop bits
Specifies time FieldServer will reserve Server side connection while
Server_Hold_Timeout
waiting for the Client side to update data in Data_Array (if
necessary)
Example
// Server Side Connections
Connections
Port
, Protocol
, Baud
P1
, SBT-FSI
, 19200
10
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available
on specific hardware.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
, Parity
, Data_Bits
, Even
, 7
Page 18 of 34
Legal Values
10
P1-P8, R1-R2
Cerberus, SBT-FSI
Yes (XLS)
No (MXL)
MXL, XLS
Yes, No
110 – 115200,
standard baud
rates only, 19200
Even, Odd, None,
Mark, Space
7, 8
1 (Vendor
limitation)
>1.0s