Appendix A.8.6.
Setting the Priority of Intrinsic Alarming
Section Title
Map_Descriptors
Column Title
Function
Pri_To_Off_Normal*
Priority for off normal events
Pri_To_Normal*
Priority for normal events
Pri_To_Fault*
Priority for faults
A BACnet EventNotification message contains a Priority field indicating the priority of the event being reported. The Priority values to be used are configured via the
Priority property of the Notification Class object, using the configuration file parameters Pri_to_offnormal, Pri_to_normal and Pri_to_fault, which determine the priorities
to be used respectively for all to-offnormal, to-normal and to-fault transitions reported via the Notification Class object.
Priority Values should be chosen as follows:
Alarm and Event Priority
Network Priority
00-63
Life Safety Message
64-127
Critical Equipment Message
128-191
Urgent Message
192-255
Normal Message