Page 1
Driver Manual (Supplement to the FieldServer Instruction Manual) FS-8704-07 ALLEN BRADLEY PCCC (TCP/IP) APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after February 2012 A Sierra Monitor Company Driver Version: 1.00 Document Revision:...
FS-8704-07 Allen Bradley PCCC (TCP/IP) Driver Manual ALLEN BRADLEY ALLEN BRADLEY PCCC (TCP/IP) DESCRIPTION The Allen Bradley PCCC (TCP/IP) driver allows the FieldServer to transfer data to and from devices over Allen Bradley PCCC (TCP/IP) Ethernet protocol. The FieldServer can emulate either a Server or Client.
HARDWARE CONNECTIONS Make sure the device IP_address is configured to be on the same IP network as the FieldServer. Use a crossover cable if the FieldServer is connected directly to the PLC device. Use a straight cable if the FieldServer is connected to a hub.
Allen Bradley PCCC (TCP/IP) Server. The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for Allen Bradley PCCC (TCP/IP) communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays”...
Other device might not be supporting the full range, e.g. SLC5 supports only 0-255 and latest PLC5 till now supports only 0-1999 FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com Page 8 of 15...
"Other device might not be supporting the full range, e.g. SLC5 supports only 0-255 and latest PLC5 till now supports only 0-1999" FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com Page 9 of 15...
Other device might not be supporting the full range, e.g. SLC5 supports only 0-255 and latest PLC5 till now supports only 0-1999 FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com Page 11 of 15...
Server map 1: N21: 0-31 Server map 2: N21: 32-100 This will panic the FieldServer and crash RS view as the DH+ will attempt to map N21: 0-100. If set up as Server Map 1: N21: 0-100, no problems are experienced.
This message is typically printed when the remote AB_TCP node is not connected to the begins.. network or is unreachable. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com Page 15 of 15 Typical Write...