Appendix A.9. Factors Determining The Reliability Property - FieldServer FS-8704-06 Driver Manual

Bacnet/ip
Hide thumbs Also See for FS-8704-06:
Table of Contents

Advertisement

FS-8704-06 BACnet IP Driver Manual

Appendix A.9. Factors Determining the Reliability Property

The Reliability Property of a BACnet object in a Server configuration is determined as follows:
For Multistate Inputs, Outputs and Values, the Reliability property is set to MULTI_STATE_FAULT (9) when the
Present_Value of the object corresponds to an entry in the Fault_Values property of the object, as configured
by the State_Text table in the configuration file.
For all object types, the Reliability property is set to COMMUNICATIONS_FAILURE (12) when the responsible
Server Node is offline.
When neither Condition 1 nor Condition 2 is met, the Reliability property is set to NO_FAULT_DETECTED (0)
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
Page 33 of 57

Advertisement

Table of Contents
loading

Table of Contents