FS-8700-16 BACnet PTP Serial Driver Manual
Example
// Data Arrays
Data_Arrays
Data_Array_Name
, Data_Array_Format
DA_AI_01
, Float
DA_AO_01
, Float
DA_DI_01
, Bit
DA_DO_01
, Bit
5.3
Server Side Connection Descriptions
Section Title
Connections
Column
Function
Title
Specify which port the device is connected
Port
to the FieldServer
Baud*
Specify baud rate
Parity*
Specify parity
Data_Bits*
Specify data bits
Stop_Bits*
Specify stop bits
Protocol
Specify protocol used
Example
// Server Side Connections
Connections
Port
, Baud
, Parity
P1
, 9600
, Even
5.4
Server Side Node Descriptors
Section Title
Nodes
Column Title
Function
3
Node_Name
Provide name for node
Node_ID
BACnet station address of physical Server node
Protocol
Specify protocol used
Node_Option
Enable or disable COV for this node
3
When using the Trane Tracer Summit Workstation System, this name will appear as the object name
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: (888) 509-1970 email: support@fieldserver.com
, Data_Array_Length
, 200
, 200
, 200
, 200
, Data_Bits
, Stop_Bits
, Protocol
, 7
, 1
, BACnet_PTP
Legal Values
P1-P8
110; 300; 600; 1200; 2400; 4800; 9600; 19200;
38400; 57600; 115000
None, Odd, Even
7, 8
1, 2
BACnet_PTP
Legal Values
Up to 32 alphanumeric characters
1 - 16777215
BACnet_PTP
COV_Enable, COV_Disable
Page 13 of 32