Appendix C.3. Liebert

Polling BACnet addresses that are not configured for Liebert systems may cause the connection to fail in older
versions of Liebert. Please contact your Liebert supplier for more information.

Appendix C.4. Honeywell EBI

Honeywell EBI cannot process EventNotifications with ACK_Required set to 1. The ACK_Required property of
Notification Class Map Descriptors configured for use with EBI must therefore be set to 0.

Appendix C.5. Using Cimetrics Explorer

Cimetrics Explorer needs to be configured to use either BACnet Ethernet or BACnet IP. This is not a setting in the
actual Cimetrics BACnet Explorer, but is done in the Cimetrics BACstac Protocol that can be found in the Local Area
Connection Properties as shown below:
Check the properties of this protocol to see what BACnet protocol is set on the Cimetrics Explorer.
To change the protocol, remove the current one and add a new one as shown below.