Status Commands - Agilent Technologies N5700 Series User Manual

System dc power supply
Hide thumbs Also See for N5700 Series:
Table of Contents

Advertisement

Status Commands

QUESTIONABLE STATUS
CONDITION
PTR/NTR
0
1
OV
1
2
OC
2
4
PF
4
16
16
OT
9
INH
512
512
10
UNR
1024
1024
STAT:QUES:COND?
STAT:QUES:PTR |:NTR <n>
STAT:QUES:PTR |:NTR ?
STANDARD EVENT
STATUS
EVENT
ENABLE
0
OPC
1
2
QYE
4
3
DDE
8
4
EXE
16
5
CME
32
7
PON
128
128
*ESR?
*ESE<n>
*ESE?
OPERATION STATUS
CONDITION
PTR/NTR
5
32
WTG
32
8
256
CV
256
10 1024
1024
CC
STAT:OPER:COND?
STAT:OPER:PTR |:NTR <n>
STAT:OPER:PTR |:NTR ?
STAT:OPER:EVEN?
Series N5700 User's Guide
Status commands program the power supply's status registers. As
shown in the following figure, the power supply has three groups of
status registers; Operation, Questionable, and Standard Event. The
Operation and Questionable status groups each consist of the
Condition, Enable, and Event registers and NTR and PTR filters.
EVENT
ENABLE
1
1
1
2
2
2
4
4
4
16
16
512
512
1024
1024
STAT:QUES:ENAB <n>
STAT:QUES:ENAB
STAT:QUES:EVEN?
OUTPUT BUFFER
Data
1
Data
4
Data
8
LOGICAL
16
OR
32
EVENT
ENABLE
32
32
LOGICAL
256
256
1024
1024
STAT:OPER:ENAB <n>
STAT:OPER:ENAB
LOGICAL
OR
ERROR QUEUE
QUEUE
QUES
NOT
EMPTY
MAV
ESB
MSS
OPER
OR
Language Reference 5
Err
ERROR
QUEUE
Err
NOT
EMPTY
Err
SERVICE
REQUEST
ENABLE
STATUS BYTE
2
4
4
3
8
8
4
16
16
5
32
32
6
RQS
64
7
128
128
*STB?
*SRE<n>
*SRE?
SERVICE
REQUEST
GENERATION
LOGICAL
OR
71

Hide quick links:

Advertisement

Table of Contents
loading