Agilent Technologies N5700 Series User Manual page 22

System dc power supply
Hide thumbs Also See for N5700 Series:
Table of Contents

Advertisement

2 Installation
Load Connections for 6V to 60V Models
WARNING
CAUTION
22
Cross
section
Resistance
(mm
)
Ω Ω Ω Ω /kilometer
2
2.5
8.21
4
5.09
6
3.39
10
1.95
16
1.24
25
0.795
35
0.565
SHOCK HAZARD Hazardous voltages may exist at the outputs and the load
connections when using a power supply with a rated output greater than 40V.
To protect personnel against accidental contact with hazardous voltages,
ensure that the load and its connections have no accessible live parts. Ensure
that the load wiring insulation rating is greater than or equal to the maximum
output voltage of the power supply.
Ensure that the load wiring mounting hardware does not short the output
terminals. Heavy connecting cables must have some form of strain relief to
prevent loosening the connections or bending the bus-bars.
All load wires should be properly terminated with wire terminals
securely attached. Do not use unterminated wires for load
connections at the power supply. The following figures illustrate how
to connect the load wires to the power supply bus-bars as well as
how to mount the bus-bar shield to the chassis.
Screws tightening torque: 104-118 in-lb.
Maximum length in meters to limit voltage to 1 V
for 5 A
for 10 A
for 20A
24.0
12.0
6.0
39.2
18.6
9.8
59.0
29.4
14.8
102
51.2
25.6
160
80.0
40.0
250
125
62.0
354
177
88.0
Wire terminal lug (2 places)
Series N5700 User's Guide
for 50A for 150A
2.4
0.8
4.0
1.4
5.8
2.0
10.2
3.4
16.0
5.4
25.2
8.4
35.4
11.8
M8x15 screw (2 places)
Flat washer
(2 places)
Flat washer (2 places)
Spring washer (2 places)
Hex Nut (2 places)

Hide quick links: