Error List
Error
0
100
101
102
104
114
203
204
205
206
209
302
351
352
353
354
118
The entire error queue is read, then emptied, using the following
command: SYST:ERR?
The following table documents the various error messages that the
power supply supports:
Device-dependent Errors (these errors set Standard Event Status register bit #3)
No error
This is the response to the ERR? query when there are no errors.
Too many channels
You have specified more channels than are installed in the mainframe.
Calibration state is off
Calibration is not enabled. The instrument will not accept calibration commands.
Calibration password is incorrect
The calibration password is incorrect.
Bad sequence of calibration commands
Calibration commands have not been entered in the proper sequence.
CAL:DATE must be yyyy/mm/dd
The calibration date must be entered in the numeric format yyyy=year, mm=month, dd=date
Compatibility function not implemented
The requested compatibility function is not available.
NVRAM checksum error
A checksum error has occurred in the instrument's nonvolatile random access memory.
NVRAM full
The nonvolatile random access memory of the instrument is full.
File not found
The internal calibration file or the internal channel attribute file was not found in NVRAM.
Output communications failure
A hardware failure has occurred on the power supply.
Option not installed
The option that is programmed by this command is not installed.
VOLT setting conflicts with VOLT:PROT setting
Attempted to program the voltage above the over-voltage protection setting.
VOLT:PROT setting conflicts with VOLT setting
Attempted to set the over-voltage protection below the voltage setting.
VOLT setting conflicts with VOLT:LIM:LOW setting
Attempted to program the voltage below the under-voltage limit setting.
VOLT:LIM:LOW setting conflicts with VOLT setting
Attempted to set the under-voltage limit above the voltage setting