208V Pdu Rack Power Configurations - HP D7171A - NetServer - LPr Manual

Rack cabling reference guide
Hide thumbs Also See for D7171A - NetServer - LPr:
Table of Contents

Advertisement

Chapter 3
Two 120 V PDUs per UPS Possible
Two 120 VAC PDUs can be plugged into the UPS in this 120 V power
configuration. There are also six NEMA 5-15R receptacles in the standard UPS
which can be used for equipment in the same rack if needed.

208V PDU Rack Power Configurations

The 208 VAC PDU power configurations appear as shown below in Table
Figure 3-6.
Recommended 208 VAC Power Configurations
In the United States, if you are using a UPS, then use PDU model E7671A or
E7672A. Attach the IEC 320 C-19 end of the E7801A cord to the PDU and attach
the L6-20 end of the same cord to the NEMA L6-20 receptacle on the UPS.
Alternate 208 VAC Power Configurations
In the 208 VAC case, without a UPS, make sure your power system has the
capacity to support the power and current needs of the components you will
power. (See the section entitled "Site Preparation: Circuit Breakers.") If capacity
is adequate, plug the PDU into a 208 V, L6-20 receptacle.
Procedure for Connecting and Routing Cables to the LH 6000r
and
3-2
43

Advertisement

Table of Contents
loading

Table of Contents