HP D7171A - NetServer - LPr Manual page 51

Rack cabling reference guide
Hide thumbs Also See for D7171A - NetServer - LPr:
Table of Contents

Advertisement

Chapter 3
Table 3-3. 230/240 VAC PDU Power and Current
1
Component
PDU
HP NetServer LH 6000r
Pentium III Xeon,
550/512K
Pentium III Xeon,
550/1MB
Pentium III Xeon,
550/2MB
HP NetServer
Mass Storage Unit
HP Console Switch
Note 1.
More ratings are listed in Table 2-9. For a full list of power ratings, see the rack
configuration utilities (for instance, Rack Assistant) on the HP Web Site.
Note 2.
Indicated current ratings are for use in selecting PDU and UPS components and
may not reflect actual measured amounts.
Description of the Recommended 230/240 VAC Configuration
Figure
shows a UPS connected to the power mains through an attached power
3-7
cord (appropriate cords are supplied for each country). The UPS has eight IEC
320 receptacles for use with the rack jumper cords. The E7671A PDU connects to
the UPS via a detachable line cord, which connects to the PDU via a C-19 plug.
This cord connects to the UPS with a C-20 plug. The 200/240 VAC PDU has two
IEC 320, C-19 and six IEC 320, C-13 receptacles for connecting rack jumper
cords.
Procedure for Connecting and Routing Cables to the LH 6000r
Model
E7675A
D9104A
D9108A
D9112A
Rack Storage/12
is D5989A
Rack Storage/
12FC is D5991A
J1497B
Power
Power
Current
(VA)
(W)
(A)
N/A
N/A
max 16
1117
1095
4.8
541
530
4.5
42
29
0.2
47
2