Power And Current For Estimating Supply Needs - HP D7171A - NetServer - LPr Manual

Rack cabling reference guide
Hide thumbs Also See for D7171A - NetServer - LPr:
Table of Contents

Advertisement

Chapter 2
In this case, use the Y-cable to connect HP Rack Storage/12 or
Rack Storage/12FC units to the PDUs.
(b) When required, a pair of Y-cables are supplied per pair of Rack
Storage/12 or Rack Storage/12FC units. That is, two Y-cables are
supplied for two units.
(c) Each Y cable connects either the two right power receptacles or the
two left power receptacles of a pair of HP Rack Storage/12 or Rack
Storage/12FC units to one receptacle on the PDU.
Table 2-5. Receptacles Needed for Units
Component
HP NetServer LH 6000r
HP Rack Storage/12
All other devices
Note 1. For 110/120 VAC, NEMA 5-15 R, for 200/240 VAC, C13
Note 2. Two Y-Cables may be used to connect two HP Rack
Storage/8 or Rack Storage/12 units to two C13 receptacles.

Power and Current for Estimating Supply Needs

When plugging devices into a PDU and UPS, do not exceed the current capacity
of the PDU nor the power output UPS. Tables 2-6 and 2-7 show the current
requirements of the common rack mounted devices.
Rack configuration utilities available from HP can help you plan the layout of
your rack. Full parts lists as well as diagrams of component positions and
details of power ratings are available. Refer to these if they are available. (See
"Rack Configuration Tools" in this chapter.)
24
Rack Cabling References
Receptacles Required
1
two
, one for each pair of
power supplies
2
two C13 or use Y-Cable
one C13