39
Warning
The sensors monitored a temperature or voltage in the warning range.
Recommended actions
•
Check that the storage system's fans are running.
•
Check that the ambient temperature is not too warm. The enclosure operating range is 41–104° F
(5–40° C).
•
Check for any obstructions to the airflow.
•
If none of the above explanations apply, replace the controller FRU that reported the error.
When the problem is fixed, event 47 is logged.
40
Error
The sensors monitored a temperature or voltage in the failure range.
Recommended actions
•
Check that the storage system's fans are running.
•
Check that the ambient temperature is not too warm. The enclosure operating range is 41–104° F
(5–40° C).
•
Check for any obstructions to the airflow.
•
If none of the above explanations apply, replace the controller FRU that reported the error.
When the problem is fixed, event 47 is logged.
41
Info.
The indicated disk has been designated a spare for the indicated vdisk.
Recommended actions
•
No action required.
43
Info.
The indicated vdisk has been deleted.
Recommended actions
•
No action required.
44
Warning
The controller contains cache data for the indicated volume but the corresponding vdisk is not online.
Recommended actions
•
Determine the reason that the disks are not online.
•
If an enclosure is down, determine corrective action.
•
If the vdisk is no longer needed, you can clear the orphan data; this will result in lost data.
•
If the volume is missing and was not intentionally removed, see
problems
on page 3.
45
Info.
A communication failure has occurred between the controller and an enclosure management processor
(EMP).
Recommended actions
•
No action required.
Resources for diagnosing and resolving
HP P2000 G3 MSA System Event Descriptions Reference Guide
7