Specifications

Video
Expansion Slots
Dimensions
System dimensions
Rack space
System weight
Cooling Specifications
Maximum heat output
Operating temperature
Operating humidity
Power Specifications
Voltage and frequency
Maximum continuous
power input
Maximum inrush current
Delayed action circuit
breaker recommended
Power availability
NOTE
Integrated 1024x768sx256 60-75hz Video, 1 meg video RAM (Cirrus
5446)
Total PCI Buses:3, Total I/O slots:10
• 4 64-bit PCI Full Length on PCI 2 (Hot Swap)
• 5 32-bit PCI Full Length on PCI 1
• 1 shared 32-bit PCI/ISA Full Length on PCI 0
12.25 in. high x 17.5 in. wide x 28 in. deep
(31.1 cm high x 44.5 cm wide x nn 71.1 deep)
7 EIA units
130 lb. (59 kg)
3675 BTU/hour
41 to 95 degrees F (5 to 35 degrees C)
20% to 80% Rh
200-240 VAC; 50/60 Hz
1100 W for a four-CPU configuration; 5.6 A at 200/208 V, 4.9 A at
230/240 V.
150 A for 4 ms
North America: a 20 A minimum circuit is to be used with one NEMA
AB1 class 14B breaker for each 16 A power distribution unit (PDU)
that is connected to an HP NetServer LXr 8000.
Europe (a single server in a rack): use a 16 A-minimum circuit with
one IEC MCB C-type breaker for each 16-amp PDU.
Europe (multiple servers in a rack): use a 16-amp-minimum circuit with
one IEC MCB D-type breaker for each 16 A PDU.
1500 DC watts continuous
Some local electrical codes do not allow a 16-amp device to be connected to a 16-
amp service. Consult a qualified electrician or local regulatory authority before
beginning electrical site preparation.