Meters Printout – [Ctrl]+[M]; Figure 7-7. System Meters - Eaton Powerware 9315 Operation Manual

200–300 kva ups
Hide thumbs Also See for Powerware 9315:
Table of Contents

Advertisement

7.6.3 Meters Printout – [Ctrl]+[M]
This key sequence prints the current readings of the UPS system meters. The input area
shows the phase-to-phase voltage, frequency, and phase current of the incoming utility,
followed by the kVA, kW, and power factor measurements. The output area shows the
same information for the power being output by the UPS. The Bypass area shows the
phase-to-phase voltage of the bypass source. The Battery area displays the DC voltage (V)
and the DC current (I). Figure 7-7 shows a sample Meters printout.
EATON Powerware
9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com
®
Uninterruptible Power System
UPS System Normal
Alarm:
None
Notice:
None
Input
VAB
VBC VCA
480
480 480
IA
IB
IC
480
480
480
KVA
KW
PF
399
379
0.95
Bypass
VAB
VBC
VCA
480
480
480

Figure 7-7. System Meters

03 JAN 1997
Output
FREQ
VAB
VBC
60.0
480
480
IA
IB
361
361
KVA
KW
300
240
Battery
V
540
Communication
14:22:49
VCA
FREQ
480
60.0
IC
IN
361
0
PF
0.80
I
+
0
7-11