Communication
7.6.4 System Information Printout – [Ctrl]+[A]
This key sequence prints a listing of all available serial data. This printout contains the
information shown on the Event History Log and System Meters screens of the UPS (both
Figure 7-6 and Figure 7-7).
7.6.5 Battery Test Printout – [Ctrl]+[B]
This key sequence prints the Battery Test Log. The log consists of a history of the last
30 battery tests that were run and the results of those tests. The most recent test appears
at the bottom of the log. Figure 7-8 shows a sample of the Battery Test Log.
The Date/Time field is the date and time of the battery test.
The Volts field is a measured value of the battery voltage during the test. This field
displays 000.0 if the test did not run to completion.
The Health field is a relative measurement of the battery condition. This number can be
used to chart the condition of the batteries. If a sudden change of this number occurs
relative to the previous test results, it is an indication that the batteries may need
attention. This display is 0.00 if the test does not run to completion.
The Data field is a value to be used by your field service engineer to gain more information
about the battery tests.
If the battery test does not complete, the Volts and Health field reads zero and the UPS
Event History Log reports either Battery Test Failed, Battery Test Aborted (Load), or Battery
Test Aborted (Utility). If the test ran to completion, Battery Passed Test appears in the UPS
Event History Log.
7-12
Uninterruptible Power System
UPS # 1
UPS System Normal
Alarm:
None
Notice:
None
Battery Test Log
Date/Time
AUG 14 23:45
SEP 11 23:45
OCT
9 23:45
NOV 13 23:45
DEC 11 23:45
JAN
8 23:45
FEB 12 23:45
MAR 12 23:41
APR
9 23:45

Figure 7-8. Battery Test Log

EATON Powerware
9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com
®
12 NOV 1997
Volts
Health
Data
498.0
1.00
0000
498.0
1.00
0000
498.0
1.00
0000
498.0
0.99
0000
498.0
0.99
0000
498.0
0.98
0000
498.0
0.98
0000
000.0
0.00
0003
496.2
0.98
0000
15:39:31