Maintaining The Ups System; Important Safety Instructions - Eaton Powerware 9315 Operation Manual

200–300 kva ups
Hide thumbs Also See for Powerware 9315:
Table of Contents

Advertisement

Chapter 8
The components inside the UPS cabinet are secured to a sturdy metal frame that is
supported by the UPS magnetics. This design allows authorized service personnel to
remove repairable components with very little disassembly. All repairable parts and
assemblies are located in the front of the UPS, allowing all routine maintenance and
servicing to be performed with front panel access.
You must schedule periodic performance checks of your UPS to keep it running properly.
Regular routine checks of operation and system parameters will enable your UPS system to
function efficiently for many trouble-free years.

8.1 Important Safety Instructions

Remember that your UPS is designed to supply power EVEN WHEN DISCONNECTED FROM
THE UTILITY POWER. The UPS interior is unsafe until the DC power source is disconnected
and the electrolytic capacitors are discharged. After disconnecting the utility power and
the DC power, authorized service personnel should wait at least five minutes before
attempting internal access to the UPS system.
EATON Powerware
9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com
®

Maintaining the UPS System

Only qualified service personnel (such as a licensed electrician) should perform the battery
installation and maintenance. Risk of electrical shock.
Batteries can present a risk of electrical shock or burn from high short-circuit current. The
following precautions should be observed: 1) Remove watches, rings, or other metal
objects; 2) Use tools with insulated handles; 3) Do not lay tools or metal parts on top of
batteries.
ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or connectors.
Attempting to alter wiring can cause injury.
Replace batteries with the same number and type of batteries as originally installed in the
UPS.
LETHAL VOLTAGE PRESENT. This UPS should not be operated with the cabinet doors open
or protective panels removed. Do not make any assumptions about the electrical state of
any cabinet in the UPS system.
If the battery cabinet requiring service was not provided by the UPS manufacturer, refer to
the battery cabinet manufacturer's operating manual for instructions on battery cabinet
installation and maintenance, or contact your Eaton service representative.
W A R N I N G
W A R N I N G
8-1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents