While in Program mode, press
for output devices (programmed in
The prompts for *81 are as follows:
81
Zone List Programming -------------------- Main Menu prompt
A 01
Zone List Number --------------------------- for entering the zone list number to be programmed
b
Zone Entry to List --------------------------- for entering zones to the assigned zone list
C
Delete Entire List? -------------------------- for deleting the entire zone list and its contents
d
Delete Specific Zones From List?-------- Selects whether to delete zones or return to next zone
E
Delete Zones ----------------------------------- for deleting specific zones from the current zone list
The following explains these prompts in detail. The left two columns identify the prompts and list the
available entries. The right-most column provides a further explanation of the entries.
Notes: (1)
Any list may include any or all of the systems zone numbers
(2)
A zone list can be assigned to more than one Powerline Carrier Device
(3)
Entering a number other than one specified will give unpredictable results.
(4)
Do not assign zones with zone types 20, 21 or 22 to a zone list.
(5)
LYNXR-SIA ONLY
Zone List 2 should be used for Cross Zoning. When creating zone list 2 for cross zoning, include only 2
zones assigned to zone types 3, 4, or 5. If interior zones (zone type 4) are cross zoned, then both
zones in zone list 2 must be interior zones. Do not cross zone more than 2 zones, or zone types that
have delays (entry/exit zones, interior w/delay), or 24-hour zones, as these choices may produce
unpredictable operation and may not function as intended. If cross zoning is used, zone list 2 should
not be used for other purposes, such as triggering powerline carrier devices. If field ✻39 has been set
to "0" (no cross zoning), then Zone List 2 can be used for other purposes.
81 to enter Zone List Menu Mode. This mode is used to program zone lists
80 Device Programming Menu Mode) or Chime-by-Zone in Zone List 3.
- 45 -
LYNXR-2 Series Installation and Setup Guide