Honeywell LYNXRPK-2 - Wireless Self-Contained Security Syste - LYNXRPK-2 - Wireless Self-Contained Security System Installation And Setup Manual
Honeywell LYNXRPK-2 - Wireless Self-Contained Security Syste - LYNXRPK-2 - Wireless Self-Contained Security System Installation And Setup Manual

Honeywell LYNXRPK-2 - Wireless Self-Contained Security Syste - LYNXRPK-2 - Wireless Self-Contained Security System Installation And Setup Manual

Installation guide

Advertisement

LYNXR-2 Series
Security Systems
Installation and Setup Guide
K15011 7/08 Rev. A

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell LYNXRPK-2 - Wireless Self-Contained Security Syste - LYNXRPK-2 - Wireless Self-Contained Security System

  • Page 1 LYNXR-2 Series Security Systems Installation and Setup Guide K15011 7/08 Rev. A...
  • Page 2: Recommendations For Proper Protection

    RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises. Recommendations for Smoke and Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
  • Page 3: Table Of Contents

    Table of Contents SYSTEM FEATURES ..........................5 MOUNTING THE CONTROL........................6 WIRING CONNECTIONS...........................7 CONNECTING/CONFIGURING COMMUNICATIONS DEVICES ............9 AC POWER AND BACKUP BATTERY....................12 INSTALLING WIRELESS ZONES......................14 MECHANICS OF PROGRAMMING ......................17 ZONE RESPONSE TYPE DEFINITIONS ....................19 DATA FIELD DESCRIPTIONS ........................21 ✻56 ENHANCED ZONE PROGRAMMING MODE ................37 ✻80 DEVICE PROGRAMMING MENU MODE ..................41 ✻81 ZONE LIST MENU MODE........................45 ✻83 ENHANCED SEQUENTIAL MODE ....................47...
  • Page 4 - 4 -...
  • Page 5: System Features

    LYNXR-2 Series Installation and Setup Guide System Features LYNXR-2 Series is not intended for UL985 Household Fire applications unless a 24-hour backup battery (P/N LYNXRCHKIT-HC or LYNXRCHKIT-SHA) is installed. Powerline Carrier Devices have not been evaluated by UL. The LYNXR-2 Series control is a self-contained, rechargeable wireless control/communicator that features easy installation and usage.
  • Page 6: Mounting The Control

    LYNXR-2 Series Installation and Setup Guide Mounting the Control Wall Mounting The illustration below shows the front assembly separated from the back plate. DO NOT disconnect the ribbon cable from the terminal strip board. Disconnect the cable only from the front assembly board.
  • Page 7: Wiring Connections

    LYNXR-2 Series Installation and Setup Guide Wiring Connections Wiring Overview The following summarizes the connections required. Refer to the Wiring Connections paragraph and the Summary of Connections diagram on the inside back cover when making connections. External sounders have not been evaluated by UL. TERMINAL STRIP TELEPHONE...
  • Page 8 LYNXR-2 Series Installation and Setup Guide Wiring Connections INCOMING PHONE LINE RING GREEN RJ31X PREMISES PHONES RING BROWN GREY DIRECT CONNECT CORD 8-POSITION JACK RING RING INCOMING PHONE LINE PREMISES PHONES 01000-008-V0 Full Line Seizure Connections Do not remove the local sounder shorting jumper (shunt). External sounders and powerline carrier devices have not been evaluated by UL LOCAL SOUNDER DISABLE: The Master Keypad’s built-in piezo sounder can be disabled by removing the shorting jumper (shunt) on the terminal board.
  • Page 9: Connecting/Configuring Communications Devices

    LYNXR-2 Series Installation and Setup Guide Connecting/Configuring Communication Modules General This LYNXR-2 Series supports central station reporting via the internet using wireless (GSM) and hardwire (IP) communications modules. It also supports upload/download programming capability via the Internet or a Private local area network (Intranet). This allows site maintenance independent of central station monitoring, and modification to sites globally via the Internet or through a private LAN.
  • Page 10 LYNXR-2 Series Installation and Setup Guide Connecting/Configuring Communication Modules AlarmNet 7845GSM, 7845i-GSM*, 7845i-ENT, 7845i or 7847i-E* Communications Device The 7845i-ENT and 7845i cannot be used for installations requiring 24-hour standby. 1. Connect the 4-wire communications cable to the LRR/IP Communications port on the LYNXR-2 Series. 2.
  • Page 11 LYNXR-2 Series Installation and Setup Guide Connecting/Configuring Communication Modules AlarmNet GSML/GSMVL Communications Device 1. Install the module into the control back plate and secure it with the three provided screws. 2. Connect the antenna to the GSML/GSMVL module. 3. Insert the antenna into the retaining slots in the control back plate. 4.
  • Page 12: Ac Power And Backup Battery

    LYNXR-2 Series Installation and Setup Guide AC Power and Backup Battery The system is powered by a 9VAC, 25VA Plug-in Transformer, ADEMCO K10145X10 (K10145CN in Canada). Refer to the wiring table below for wire gauge and length. Wire Gauge Distance from Transformer to Control Up to 75 feet 75 to 150 feet 150 to 300 feet...
  • Page 13 LYNXR-2 Series Installation and Setup Guide AC Power and Backup Battery AC Power and Rechargeable Backup Battery The LYNXR-2 Series is equipped with an integral, replaceable, rechargeable battery pack rated at 7.7Vdc. Select the appropriate battery pack, based on the installation’s requirement, and install the battery pack. Model/Part Number Battery StandbyTime Low Battery Notification...
  • Page 14: Installing Wireless Zones

    LYNXR-2 Series Installation and Setup Guide Installing Wireless Zones General Information Zones: The control supports up to 24 wireless zones using 5800 Series transmitters, and up to 16 wireless buttons. Range: The built-in RF receiver can detect signals from wireless transmitters within a nominal range of 200 feet.
  • Page 15 LYNXR-2 Series Installation and Setup Guide Installing Wireless Zones • Button-type transmitters should be periodically tested for battery life. The 5801, 5802MN, 5802MN2, 5804, 5804BD, 5804BDV, and 5804E button transmitters have replaceable batteries. Using the Transmitter Sniffer Mode Use this mode after all transmitters have been entered to check that all transmitters have been properly programmed.
  • Page 16: Series Transmitter Loop Numbers

    LYNXR-2 Series Installation and Setup Guide Installing Wireless Zones 5800 Series Transmitter Loop Numbers (Refer to this information when programming transmitters) The following illustration shows the compatible transmitters, their associated input types and loop designations. LOOP 3 LOOP 4 YOU MUST LOOP 2 ENROLL LOOP...
  • Page 17: Mechanics Of Programming

    LYNXR-2 Series Installation and Setup Guide Mechanics of Programming General Programming Information Programming options are stored in non-removable, electrically erasable, nonvolatile EEROM memory. The system can be programmed at any time, even at the installer's premises prior to the actual installation. Simply apply power temporarily to the Control and then program the unit as desired.
  • Page 18: Loading Factory Defaults

    LYNXR-2 Series Installation and Setup Guide Mechanics of Programming Interactive Menu Mode Programming ( ✻ , ✻ , ✻ , ✻ , ✻ , ✻ (i.e., ✻56). The keypad will display the first of a series of prompts. A detailed [✻] + interactive mode No.
  • Page 19: Zone Response Type Definitions

    LYNXR-2 Series Installation and Setup Guide Zone Response Type Definitions General Information During programming, you must assign a zone type to each zone, which defines the way in which the system responds to faults in that zone. Zone types are defined below. Type 00 Zone type 00 is used to program a zone that is not used.
  • Page 20 LYNXR-2 Series Installation and Setup Guide Zone Response Type Definitions Zone type 09 can be assigned to any wireless zone used as a fire zone. This zone type Type 09 is always active and cannot be bypassed. Supervised Fire Zone Characteristics: •...
  • Page 21: Data Field Descriptions

    LYNXR-2 Series Installation and Setup Guide Data Field Descriptions The following pages list all data fields in this Control (in numerical order). Use the blank programming form to record the data for this installation. Specific fields include options for programming that are unique to the LYNXR-2SIA version.
  • Page 22 LYNXR-2 Series Installation and Setup Guide Data Field Descriptions ✻29 Enter # + 10 for 10, # + 11 for 11, and # + 12 for 12. Daylight Savings Time Start/ End Month 0 = do not display the time 1 = display the time ✻30 Daylight Savings Time Start/...
  • Page 23 LYNXR-2 Series Installation and Setup Guide Data Field Descriptions ✻35 The system will wait the time entered before sounding alarm Entry Delay 01 upon entering if system is not disarmed. LYNXR-2 SELECTIONS UL installations: must be set for a maximum of 45 seconds 00-99 = entry delay time in seconds.
  • Page 24 LYNXR-2 Series Installation and Setup Guide Data Field Descriptions ✻ Field 39: Field *39 is used to program different features in the LYNXR-2 and LYNXR-2SIA controls. Please be sure that you use the correct field for the control being installed. ✻39 When the system powers up armed, an alarm will occur 1 minute after Power Up In Previous State...
  • Page 25 LYNXR-2 Series Installation and Setup Guide Data Field Descriptions If the GSM/IP (Digital Communication with AAV) feature is used (options 5 and 7 in *55), there may be restrictions when dialing the numbers entered in *41, *42 and *46 (i.e.; #, ✻ , pause may not be allowed, or phone number extensions may not be dialed, etc) depending on the service provider.
  • Page 26 LYNXR-2 Series Installation and Setup Guide Data Field Descriptions ✻ Field *47 is used to program different options in the LYNXR-2 and LYNXR-2SIA controls. Please Fields be sure that you use the correct field for the control being installed. ✻47 This option is used to enter the correct type of phone dialing Phone System Select (pulse or tone), and to select the correct WATS line option for...
  • Page 27 LYNXR-2 Series Installation and Setup Guide Data Field Descriptions ✻49 This field is used to select a reporting option as follows: Split/Dual Reporting Enter: 0 - 5 when reporting to telephone receivers. To Primary To Secondary 6 - 9 when reporting to a pager is desired. 0 = All reports None, unless primary fails, 10 - 13 when reporting to an aux telephone receiver.
  • Page 28 LYNXR-2 Series Installation and Setup Guide Data Field Descriptions ✻51 Test report code entered in field ✻ 64 is sent. Periodic Test Report 0 = no test report 1 = once every 24 hrs 2 = weekly 3 = once every 30 days ✻52 Select the time for the first report following programming or First Test Report Offset...
  • Page 29 LYNXR-2 Series Installation and Setup Guide Data Field Descriptions ✻55 This option is used to enable/disable Central Station reporting via Reporting Channels the LRR/IP Communications Device (See Field *77). Upload/ 0 = Telco Line (no Radio) download via the Internet IP module is not affected by this entry. 1 = LRR/IP(Digital Communication only) and Telco Line The option specifies the channel that the control will use when 3 = LRR/IP (Digital Communication only) (no Telco Line)
  • Page 30 LYNXR-2 Series Installation and Setup Guide Data Field Descriptions With an Expanded or 4+2 Format: Enter codes in both boxes (1st and 2nd digits) for 1–9, or A–F, as described above. Entering "0" in the first box will disable a report. Entering "0" in the second box will eliminate the expanded message for that report.
  • Page 31 LYNXR-2 Series Installation and Setup Guide Data Field Descriptions ✻62 Timing of this report is random with up to a 4-hour delay. If AC restores AC Loss Report Code before the report goes out, there is no AC restore report. (See notes above) ✻63 This will be sent when a low battery condition exists in the system’s...
  • Page 32: Test Restore Report Code

    LYNXR-2 Series Installation and Setup Guide Data Field Descriptions ✻75 Sent when a transmitter that previously sent in a “low battery” RF Transmitter Low Battery message has sent a message indicating it no longer has a low battery Restore Report Code condition.
  • Page 33 LYNXR-2 Series Installation and Setup Guide Data Field Descriptions 1. If the LRR/IP communications device is selected as the preferred channel option and the APX32EN detects a communication failure or supervision failure, reports will be sent to the Primary Phone without any delay. 2.
  • Page 34 LYNXR-2 Series Installation and Setup Guide Data Field Descriptions ✻90 Example: To select “Alarm/Alarm Restore” and “Open/Close,” enter 9 (1 Event Logging Options + 8); to select all events, enter #15. 0 = No event logging Default “3” = alarm/alarm restore (1) plus trouble/trouble restore (2). 1 = log Alarm/Alarm Restore The system has the ability to record various events in a history log (84- 2 = log Trouble/Trouble Restore...
  • Page 35 LYNXR-2 Series Installation and Setup Guide Data Field Descriptions ✻ ✻ DOWNLOAD INFORMATION ( ✻94 This is the phone number the control will use to call back the Download Call Back Phone Number downloading computer. Enter up to 20 digits as follows: 0–9, # +11 for “*”, # + 12 Do not fill unused spaces.
  • Page 36 LYNXR-2 Series Installation and Setup Guide ✻ 56 Enhanced Zone Programming Mode This is an interactive menu mode that is used to program zone numbers, zone types, alarm and report codes, and to identify the type of loop input device. This mode can also be used for entering 5800 Series transmitter serial numbers.
  • Page 37: Enhanced Zone Programming Mode

    LYNXR-2 Series Installation and Setup Guide ✻ 56 Enhanced Zone Programming Mode ✻ Refer to the zone assignment table for 56 on the separate programming form. ✻ The following explains the 56 prompts in detail. The left column identifies the prompts and lists the available entries for each.
  • Page 38 LYNXR-2 Series Installation and Setup Guide ✻ 56 Enhanced Zone Programming Mode This prompt can be used to enroll loop number and serial number via RF transmission or the loop number can be enrolled manually. If using the RF Learning Mode, there is no need to manually enter a loop number.
  • Page 39 LYNXR-2 Series Installation and Setup Guide ✻ 56 Enhanced Zone Programming Mode If “L” is displayed, the serial number for this transmitter has already been entered. It IA LC may, however, still be viewed, confirmed (only if in listen mode), or deleted. View serial number Enroll Mode Enter “3”.
  • Page 40 LYNXR-2 Series Installation and Setup Guide ✻ 56 Enhanced Zone Programming Mode † see ✻84 Assign Zone Voice Descriptors section for vocabulary index Use the [6] or [8] key to advance as described. To change the entered index number before pressing [6] or [8], simply press [#] + Descriptor 1 desired 2-digit vocabulary index number.
  • Page 41: Device Programming Menu Mode

    LYNXR-2 Series Installation and Setup Guide ✻ 80 Device Programming Menu Mode Powerline Carrier Devices (e.g.; X10 brand devices) are programmable switches that can be used to perform many different functions. They can be used to turn lights on and off, control sounders, or for status indications.
  • Page 42 LYNXR-2 Series Installation and Setup Guide ✻ 80 Device Programming Menu Mode The "STOP" programming determines when and under what conditions the device will be STOP deactivated. The following options are available: Upon Restore of a Zone List Restore Zone List: If a "ZONE LIST" is used as the “Stop” event, the device will de-activate when all the zones in that list restore from a previous fault, trouble, or alarm condition.
  • Page 43 LYNXR-2 Series Installation and Setup Guide ✻ 80 Device Programming Menu Mode The following explains these prompts in detail. The left two columns identify the prompts and list the available entries. The right-most column provides a further explanation of the entries. Note: Entering a number other than one specified will give unpredictable results.
  • Page 44 LYNXR-2 Series Installation and Setup Guide ✻ 80 Device Programming Menu Mode If a zone type or system operation will be used to start the device action, enter the appropriate 2-digit code for the device being programmed (see table that follows). Choices for zone types Start Zone Type 00 = Not Used...
  • Page 45: Zone List Menu Mode

    LYNXR-2 Series Installation and Setup Guide ✻ 81 Zone List Menu Mode While in Program mode, press ✻ 81 to enter Zone List Menu Mode. This mode is used to program zone lists ✻ for output devices (programmed in 80 Device Programming Menu Mode) or Chime-by-Zone in Zone List 3. The prompts for *81 are as follows: Zone List Programming -------------------- Main Menu prompt A 01...
  • Page 46 LYNXR-2 Series Installation and Setup Guide ✻ 81 Zone List Menu Mode Pressing 1 advances to the next prompt below. Pressing 0 exits mode, upon which this prompt blinks, indicating the mode is inactive. Zone List Programming 0 = exit mode 1 = enter mode Enter the Zone List Number 01, 02, or 03 to program (or 00 if no zone lists are used).
  • Page 47: Enhanced Sequential Mode

    LYNXR-2 Series Installation and Setup Guide ✻ 83 Enhanced Sequential Mode By using this mode, you can add, delete, or change the serial number of a transmitter in a zone, but retain all other existing data that has been programmed for that zone. Note that the ✻...
  • Page 48 LYNXR-2 Series Installation and Setup Guide ✻ 83 Enhanced Sequential Mode Enter the 2-digit zone number of the first transmitter to have its serial number A 02 entered. The system will announce the Voice Descriptor for the selected zone number, if it is programmed.
  • Page 49 LYNXR-2 Series Installation and Setup Guide ✻ 83 Enhanced Sequential Mode This prompt can be used to enroll the transmitter serial number via RF transmission or manually. If using the RF Learning Mode there is no need to manually enter a serial number.
  • Page 50: Assign Zone Voice Descriptors

    LYNXR-2 Series Installation and Setup Guide ✻ 84 Assign Zone Voice Descriptors Use this mode to assign voice descriptors for each zone. These are the descriptors that are announced when the system announces any event involving a zone number. Each descriptor can consist of up to 3 words.
  • Page 51: Voice Vocabulary Index

    LYNXR-2 Series Installation and Setup Guide ✻ 84 Assign Zone Voice Descriptor Enter the last word of the descriptor for the selected zone. Use the [6] or [8] key to advance as described. To change the entered index number before pressing [6] or [8], simply press Descriptor 3 [#] + desired 2-digit vocabulary index number.
  • Page 52: Record Custom Voice Descriptors

    LYNXR-2 Series Installation and Setup Guide ✻ 85 Record Custom Voice Descriptors Use this mode to record up to 5 custom voice descriptors. To enter this mode, enter ✻ 85 while in Programming mode. Note: Entering a number other than one specified will give unpredictable results. Entering “1”...
  • Page 53: Remote Programming/Control (Downloading)

    LYNXR-2 Series Installation and Setup Guide Remote Programming/Control (Downloading) General Information The control panel can be remotely programmed from an IBM-compatible Personal Computer (PC), Compass Downloader, a HAYES Modem or via a capable GSM or IP communications device. Downloading may only be performed if a technician is at the site. Multiple security levels protect remote programming against compromise by attempts to defeat the system.
  • Page 54: Remote Programming Advisory Notes

    LYNXR-2 Series Installation and Setup Guide Remote Programming/Control (Downloading) • Command the system to upload a copy of its resident program to the office. • Set the time • View/Modify • X10/ Scheduling • Read: arming status, AC power status, lists of faulted zones, bypassed zones, zones currently in alarm, zones currently in trouble, and RF sensors with low battery conditions;...
  • Page 55: System Operation

    LYNXR-2 Series Installation and Setup Guide System Operation Keypad Operation The keypad allows the user to arm and disarm the system, and perform other system functions, such as bypassing zones. Zone and system conditions (alarm, trouble, bypass) are displayed in the display window. When an alarm occurs, keypad sounding and external sounding will occur, and the zone(s) in alarm will be displayed on the keypad.
  • Page 56: Remote Phone Control Feature

    LYNXR-2 Series Installation and Setup Guide System Operation Security Code Notes • The Master and Secondary security codes permit access to the system for arming, disarming, etc. • The Installer Code can disarm the system only if it was used to arm it. In addition, the Installer Code cannot disarm the system if it was armed by pressing and holding a Quick-Arm button.
  • Page 57 LYNXR-2 Series Installation and Setup Guide System Operation Remote Phone Control Keypad Functions + [1] To remotely disarm system: + [2] To remotely arm in AWAY mode: + [3] To remotely arm in STAY mode: + [2] or [3] + [0] To remotely arm in AWAY or STAY with no delay: [#] + [4] + (2-digit) device no.
  • Page 58: System Displays

    LYNXR-2 Series Installation and Setup Guide System Operation System Displays Display Meaning Remote Phone Control feature is active (Appears in place of the clock). System Speaker Phone mode is active (Appears in place of the clock). AC power is present. If not displayed, the system is operating on backup battery power. ALARM System is armed and an intrusion has been detected (also appears during a fire alarm or audible emergency alarm).
  • Page 59 LYNXR-2 Series Installation and Setup Guide System Operation Operator Commands The Central Station operator begins the session, which last 5 minutes, by entering one of the valid AAV commands shown in the table below. The session may be extended 5 minutes, without changing the operating mode, by pressing the [7] key on the touch-tone phone.
  • Page 60: Keypad Function Summary

    LYNXR-2 Series Installation and Setup Guide Keypad Function Summary A summary of system functions is provided below. For more detailed information refer to the User Guide. Security Functions (Empty boxes represent the user’s security code) (high level messages); press again for secondary messages Checking system status: ......
  • Page 61: Testing The System

    LYNXR-2 Series Installation and Setup Guide Testing the System Test Mode After installation is completed, the security system should be carefully tested, as follows. 1. With the system in the disarmed state, check that all zones are intact. If the READY LED is not lit, press the [ ✻...
  • Page 62: System Communication

    LYNXR-2 Series Installation and Setup Guide System Communication This section provides an explanation of formats this system accommodates for reporting alarms and other system conditions to the central station. The process of a successful transmission consists of both the method of communication between the control panel and the central station receiver, and the actual way the information is sent and displayed at the central station.
  • Page 63 LYNXR-2 Series Installation and Setup Guide System Communication The following table shows the message formats for 3+1, 4+1 and 4+2 reports, where: SSS or SSSS = Subscriber ID C = Close Code (1st Digit) A = Alarm Code (1st digit) U = User Number (in hex) Z = Typically Zone Number* (2nd digit) G g = Test Code (1st &...
  • Page 64 LYNXR-2 Series Installation and Setup Guide System Communication ADEMCO Contact ID® Reporting takes the following format: CCCC Q EEE GG ZZZ where: CCCC = Customer (subscriber) ID Q = Event qualifier, where: E = new event, and R = restore EEE = Event code (3 hex digits) (for a complete list of event codes, refer to the central office receiver manual) GG = Always “00”...
  • Page 65: Troubleshooting Guide

    LYNXR-2 Series Installation and Setup Guide Troubleshooting Guide Trouble Conditions The word “FAULT” on the keypad’s display, accompanied by a rapid “beeping” at the keypad, indicates that there is a trouble condition in the system. Pressing any key can silence the audible warning sound. Instruct users to call for service immediately upon seeing any of the following messages.
  • Page 66 LYNXR-2 Series Installation and Setup Guide Troubleshooting Guide S y s t e m ( i n c l u d i n g W i r e l e s s ) SYMPTOM POSSIBLE CAUSE REMEDY 1a. Transmitter not properly powered. Check or change transmitter's battery.
  • Page 67: Smoke Detectors

    LYNXR-2 Series Installation and Setup Guide Troubleshooting Guide C o n t r o l SYMPTOM POSSIBLE CAUSE REMEDY The word “AC” is not 1a. Interrupted AC power supply. 1a. Check transformer connection and displayed. powerline circuit breaker. 2a. System in Test mode. 2a.
  • Page 68: Programming Default Tables

    LYNXR-2 Series Installation and Setup Guide Programming Default Tables LYNXR-2 Control Defaults (boldface indicates defaults that differ between tables) Function Table 1 Table 2 Table 3 Table 4 *20 Installer code 4112 4112 4112 4112 *21 Quick arm enable *22 Keypad backlight timeout *23 Forced bypass *24 RF house ID code *25 Powerline carrier device house code...
  • Page 69 LYNXR-2 Series Installation and Setup Guide Programming Default Tables LYNXR-2 Control Defaults (boldface indicates defaults that differ between tables) Function Table 1 Table 2 Table 3 Table 4 *87 Auxiliary Function/ 1-button paging *88 Pager characters *89 Event log 80% full report code *90 Event logging *91 Alarm audio verification/remote phone control *92 Number of reports in armed period...
  • Page 70: Lynxr-2Sia Control Defaults

    LYNXR-2 Series Installation and Setup Guide Programming Default Tables LYNXR-2SIA Control Defaults (boldface indicates defaults that differ between tables) Function Table 1 Table 2 Table 3 Table 4 *20 Installer code 4112 4112 4112 4112 *21 Quick arm enable *22 Keypad backlight timeout *23 Forced bypass *24 RF house ID code *25 Powerline carrier device house code...
  • Page 71 LYNXR-2 Series Installation and Setup Guide Programming Default Tables LYNXR-2SIA Control Defaults (boldface indicates defaults that differ between tables) Function Table 1 Table 2 Table 3 Table 4 *84 Assign zone voice descriptors Refer to *84 Programming *86 Multi-mode (E-mail notification) *87 Auxiliary Function/ 1-button paging *88 Pager characters *89 Event log 80% full report code...
  • Page 72 LYNXR-2 Series Installation and Setup Guide Programming Default Tables ✻56 ZONE ASSIGNMENT/ALARM REPORT CODES FOR TABLE 1 Zone No. Zone Type Alarm Code Input Type Loop Number Zone Descriptor 3 (RF) 47, 04 (FRONT DOOR) 3 (RF) 33, 04 (BACK DOOR) 3 (RF) 80 (WINDOW) 3 (RF)
  • Page 73 LYNXR-2 Series Installation and Setup Guide Programming Default Tables ✻80 DEFAULT TABLE: APPLIES TO DEFAULT TABLE 1 and 2 (devices 01-07 have no default values, devices 09-15 have all default values set to 00) Start Stop Zone Type Restore of Zone type Device Number Action...
  • Page 74: Regulatory Agency Statements

    LYNXR-2 Series Installation and Setup Guide Regulatory Agency Statements FCC STATEMENT THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
  • Page 75: Limitations Of This System Statement

    LYNXR-2 Series Installation and Setup Guide WARNING THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons.
  • Page 76: Ul Notices

    LYNXR-2 Series Installation and Setup Guide UL NOTICES 1. For UL Residential Burglar Alarm installations with line security, total exit delay time must not exceed 60 seconds. For UL Burglar Alarm installations without line security, total exit delay time must not exceed 120 seconds. 2.
  • Page 77: Contacting Technical Support

    Note the proper model number of this product, and the version level (if known) along with any documentation that came with the product. • Note your Honeywell customer number and/or company name. Having this information handy will make it easier for us to serve you quickly and effectively.
  • Page 78 LYNXR-2 Series Installation and Setup Guide – Notes – - 78 -...
  • Page 79 LYNXR-2 Series Installation and Setup Guide – Notes – - 79 -...
  • Page 80 LYNXR-2 Series Installation and Setup Guide – Notes – - 80 -...
  • Page 81 LYNXR-2 Series Installation and Setup Guide – Notes – - 81 -...
  • Page 82 LYNXR-2 Series Installation and Setup Guide – Notes – - 82 -...
  • Page 83: Index

    LYNXR-2 Series Installation and Setup Guide – Index – *56 enhanced zone programming mode ... 14, 18, 29, 36 Busy-standby ..............65 * 80 device programming......18, 41, 42, 43, 44 Button transmitters ............. 14, 15 Button type ................. 37 *81 zone list menu mode..........18, 45 Button zones ...............
  • Page 84 LYNXR-2 Series Installation and Setup Guide Factory defaults ..............18 Open report code ............68, 70 Fault ................58, 65 Operator commands ............59 FC ..................62 Optima 24 Pplus FAX96 modem........53 FCC statement ..............74 Other features ..............5 Features ................5 Other functions..............56 Fire sounder timeout ............68, 70 First test report offset...........68, 70 Flexible callback ..........34, 53, 69, 71...
  • Page 85 LYNXR-2 Series Installation and Setup Guide Scheduling..............54, 58 Technical support ............... 77 Secondary phone number ..........68, 70 Telco handoff ..............53 Secondary subscriber account number......68, 70 Temporal pulse ..............22 Secondary user codes ............55 Test mode............60, 61, 66, 67 Security code handshake ............53 Test report code ............
  • Page 86: Specifications

    LYNXR-2 Series Installation and Setup Guide Specifications LYNXR-2 Series 1. Physical: 10-3/8” W x 7-1/8” H x 1-3/4” D Security Controls 2. Electrical: VOLTAGE INPUT: 9VAC from plug-in 25VA transformer. RECHARGEABLE BACKUP BATTERY: Nickel-metal hydride battery pack rated at 7.7Vdc. ALARM SOUNDER: Piezo = 6-14VDC, 30mA max/ Bell = 6-14VDC, 120mA max (e.g., ADEMCO’s WAVE2EX).
  • Page 87: Summary Of Connections Diagram

    BLACK DEVICES CARRIER YELLOW POWERLINE DATA DATA Notes: Connection of the fire alarm signal to a fire alarm headquarters or a central station shall be permitted with the approval of the local authority having jurisdiction. The burglar alarm signal shall not be connected to a police emergency number.
  • Page 88 WARRANTY INFORMATION For the latest warranty information, please go to: www.honeywell.com/security/hsc/resources/wa 2 Corporate Center Drive, Suite 100 P.O. Box 9040, Melville, NY 11747 Copyright © 2008 Honeywell International Inc. www.honeywell.com/security ÊK15011sŠ K15011 7/08 Rev. A...

This manual is also suitable for:

Lynxr-2 series

Table of Contents