Refer to the zone assignment table for
The following explains the
available entries for each. The right column provides a further explanation of the entries.
Note: You may find it convenient to adjust the volume setting before entering the Programming Mode. This will allow you to
clearly hear feedback announcements or system beeps.
ZT16 is only available on the LYNXR-2SIA version of the control panel.
A 02
Zone Number
02-41, 95, 96, 99 = Zone number
[✻] = continue
00 = exit Zone Programming mode
b
zt
Zone Type
00-24 = zone type
[✻] = continue
[#] = return to previous prompt
Note: If 00 is accepted as a zone type, save
the 00 zone type and advance to the
confirm delete prompt (F).
rc
C
Report Code
Enter the report code for this zone.
[✻] = continue
[#] = return to previous prompt
d
i
Input Type
3 =RF (supervised RF) – sends periodic
check-in signals, faults, restore and low
battery signals
4 = UR (unsupervised RF) – sends same as
"RF" type, but control does not supervise
the check-in signals
5 = BR (button type) – sends only fault and
low battery signals; does not send
restores or check-in signals
[✻] = continue
[#] = return to previous prompt
✻ 56 Enhanced Zone Programming Mode
✻
56 on the separate programming form.
✻
56 prompts in detail. The left column identifies the prompts and lists the
Enter the 2-digit zone number to be programmed and the Voice Descriptor for the
selected zone number will be announced, if it is programmed. Press [✻] to advance.
•
Zones 02-25 = RF zones (only)
•
Zones 26-41 = Button zones (only)
•
Zone 92 = Duress
•
Zones 95, 96, 99 = Panic zones
Pressing 00 exits mode, upon which the prompt "56" blinks, indicating the mode is
inactive. Press [✻] + any field number to go to that field.
Each zone must be assigned to a zone type, which defines the way in which the system
responds to faults in that zone. Enter the 2-digit zone type for this zone as follows:
00 = Not Used
01 = Entry/Exit #1
02 = Entry/Exit #2
03 = Perimeter
04 = Interior Follower
05 = Trouble Day/Alarm Night
06 = 24 Hr Silent
07 = 24 Hr Audible
08 = 24 Hr Aux
-
Notes: (1) ZT16 is only available on the LYNXR-2SIA version
(2) ZT16 is not for use with manually actuated devices including fire, keypad or
SIA ZT 16 must be used in SIA fire applications.
The report code consists of 2 hexadecimal digits, each in turn consisting of 2
numerical digits. For example, for a report code of "3C", enter [0][3] for "3" and [1][2]
for "C".
If this is Zone 95, 96 or 99, the system skips to the VOICE DESCRIPTOR prompt (1C).
Enter the input type for the transmitter assigned to this zone. Refer to the
transmitter's instructions for input types of each transmitter.
Notes: (1) RF type transmitters must remain within range of the receiver, otherwise a
supervision failure signal will occur.
(2) UR and BR type transmitters may be carried off premises (out of range
without causing a supervision failure.
(3) Zones 2-25 should be assigned Input Type 3 or 4. Zones 26-41 should be
assigned Input Type 5 only.
LYNXR-2 Series Installation and Setup Guide
09 = Fire without verification
10 = Interior w/Delay
14 = Carbon Monoxide
16 = Fire with verification
20 = Arm–Stay
21 = Arm–Away
22 = Disarm
23 = No Alarm Response
24 = Silent Burglary
key fob zones, or fire pull stations, or for heat detectors.