✻56 Enhanced Zone Programming Mode
This is an interactive menu mode that is used to program zone numbers, zone types, alarm and report codes,
and to identify the type of loop input device. This mode can also be used for entering 5800 Series transmitter
serial numbers.
Note: There are two methods for entering transmitter serial numbers. The first method is by using ✻56 Enhanced Zone
Programming Mode (described below). The second method is by using ✻83 Enhanced Sequential Mode. Note that the
✻83 Enhanced Sequential Mode requires that all zone information first be entered using ✻56 Enhanced Zone
Programming mode.
While in Program mode, press
prompts in detail. The left column identifies the prompts and the right column provides an explanation of
the entries and lists the available entries.
1. ZT16 is only available on the LynxSIA Plus version of the control panel.
2. Prompts d, E, F, 1A, 1b, 1C, 1d, 1E, AND 1F do not apply to Zones 92, 95, 96 or 99.
3. Prompts d, E, F, 1A and 1b do not apply to Zone 1 (hardwire zone).
A A A A 01 01 01 01
ZONE
ZONE
ZONE
ZONE NUMBER
NUMBER
NUMBER
NUMBER
b
ZONE
ZONE TYPE
TYPE
ZONE
ZONE
TYPE
TYPE
C C C C
REPORT
REPORT
REPORT CODE
REPORT
CODE
CODE
CODE
56 to enter Zone Programming Menu Mode. The following explains the
Zone Number
Enter the 2-digit zone number to be programmed and the Voice Descriptor for the selected
zone number will be announced, if it is programmed. Press [✻] to advance to the next
field. Pressing 00 exits mode, upon which the prompt "56" blinks, indicating the mode is
inactive. Press [✻] + any field number to go to that field.
SELECTIONS
00 = Exit Zone Programming
01 = Hardwire Zone
02-25 = RF zones (only)
Zone Type
Each zone must be assigned to a 2-digit zone type, which defines the way in which the
system responds to faults in that zone. Press [✻] to advance to the next field or [#] to
return to previous prompt.
Notes: (1) ZT16 is only available on the LynxSIA Plus version
(2) ZT16 is not for use with manually actuated devices including fire, keypad or key
fob zones, or fire pull stations, or for heat detectors.
(3) If 00 is accepted as a zone type, save the 00 zone type and advance to the
confirm delete prompt (F).
SIA ZT 16 must be used in SIA fire applications.
SELECTIONS
00 = Not Used
01 = Entry/Exit #1
02 = Entry/Exit #2
03 = Perimeter
04 = Interior Follower
05 = Trouble Day/Alarm Night
06 = 24 Hr Silent
07 = 24 Hr Audible
08 = 24 Hr Aux
-
Report Code
Enter the report code for this zone. The report code consists of 2 hexadecimal digits, each
in turn consisting of 2 numerical digits. For example, for a report code of "3C", enter
[0][3] for "3" and [1][2] for "C". If this is Zone 95, 96 or 99, the system skips to the VOICE
DESCRIPTOR prompt (1C). Press [✻] to advance to the next field or [#] to return to
previous prompt.
Note:
If "00" is entered as the first digit, there will be no report for that zone.
SELECTIONS
00-09 = 0-9
12 = C
10 = A
13 = D
11 = B
26-41 = Button zones (only)
92 = Duress
95, 96, 99 = Panic zones
09 = Fire without verification
10 = Interior w/Delay
14 = Carbon Monoxide
16 = Fire with verification
20 = Arm–Stay
21 = Arm–Away
22 = Disarm
23 = No Alarm Response
24 = Silent Burglary
14 = E
15 = F