Using A Firmware Upgrade Tape (Drive Firmware Only) - HP C7745NB - SureStore DLT Tape Autoloader 1/9 Manual

Hp surestore tape autoloader model 1/9 upgrade and parts replacement guide
Hide thumbs Also See for C7745NB - SureStore DLT Tape Autoloader 1/9:
Table of Contents

Advertisement

Using a Firmware Upgrade Tape
(Drive Firmware Only)
1. Call your service representative to get the drive upgrade tape.
2. Ensure that you have removed all tapes from the drive.
If a tape is in the drive, use the front panel display to return the tape
to a storage slot. From the front panel, go to the following menus.
Operations ->
Drive and Tape Operations ->
Unload Tape from Drive
3. Load the firmware upgrade tape into an empty slot in the autoloader.
Note the slot number.
4. Use the following menu to perform the firmware upgrade:
Main Menu ->
Administration ->
Upgrade Drive Firmware
5. From the
Upgrade Drive Firmware
the slot containing the firmware upgrade tape. Select
6. Watch the upgrade status on the autoloader's front panel. The tape
will return to the original storage slot when the procedure is
complete.
7. Remove the firmware upgrade tape from the autoloader.
8. Power-cycle the autoloader.