Generators; Basic 120 Vac Generator Hookup (Off-Grid Applications Only); Figure 3-14 Basic 120 Vac Generator Block Diagram (For Off-Grid Applications) - Xantrex7 UX - REV A Owner's Manual

Inverter/charger
Table of Contents

Advertisement

3.0 Installation

Generators

Basic 120 Vac Generator Hookup (Off-Grid applications only)

NOTE: The ground and neutral
must be bonded at one
place, and only one place, in
the system. If the generator
is the main source of power,
(i.e., no utility grid power)
then the neutral and ground
connections are bonded at
the generator. If the
generator is acting as a
backup for the utility grid,
then the bond should be at
the main utility breaker box.
In this case, ensure that no
bond exists at the generator
output.
120 VAC
GENERATOR
Neutral/
Ground bond
Basic 120 Vac Generator Block Diagram (for Off-Grid applications)
©2002 Xantrex Technology Inc. All Rights Reserved.
P/N 975-0026-01-01 Rev A 06/2002
1.
Connect the ground wire on the generator to the GROUND terminal on the
inverter.
2.
Connect the generator neutral wire to the NEUTRAL terminal on the inverter.
3.
Connect the generator HOT wire to the HOT input on the inverter.
4.
Bond the neutral to the ground on the output of the generator (only if used in
non-utility installations) or in the main utility breaker box (not both).
5.
Drive a ground rod 6–8 feet (1.8 - 2.4 meters) into the ground and connect the
generator's ground to the ground rod.
6.
Start the generator and check for proper operation of the inverter (i.e., the
inverter transfers from battery to generator power).
HOT
Neutral
Ground
Figure 3-14
INVERTER/
CHARGER
HOT
Neutral
Ground
120 VAC
LOADS
45