AC Wiring (continued)

AC Output Wiring to the Sub-panel

WARNING: ENSURE THE
SUB-PANEL DOES NOT
HAVE A NEUTRAL TO
GROUND BOND. IF IT
DOES, REMOVE IT. ALL AC
NEUTRAL-GROUND
BONDING IS DONE AT THE
MAIN UTILITY BREAKER
BOX (SERVICE ENTRANCE).
NOTE: The two neutral
connections (input and
output) are common to one
another and may be used in
any combination.
©2002 Xantrex Technology Inc. All Rights Reserved.
P/N 975-0026-01-01 Rev A 06/2002
1.
Connect the GROUND wire to the inverter's AC GROUND chassis
terminal. Connect the other end of this wire to the GROUND bus in the
sub-panel.
2.
Connect the NEUTRAL (white) wire to the inverter's NEUTRAL
OUTPUT terminal. Connect the other end of this wire to the NEUTRAL
bus in the sub-panel.
3.
Connect the HOT (black) wire to the inverter's terminal labeled AC
HOT OUTPUT. Connect the other end of this wire to the sub-panel's
input circuit breaker.
4.
Torque all inverter terminal block connections to 16 inch-pounds.
Refer to the sub-panel manufacturer's specifications for wire torques at
the sub-panel.
AC Ground NEUTRAL
Figure 3-12
AC Output Wiring
HOT
OUT
OUT
43